LiftMaster CAPXS Smart Video Intercom S, a cloud based access control video intercom with touchscreen display and camera
LiftMaster CAPXS Smart Video Intercom S. Product image from All Security Equipment.

Documentation Information

Manufacturer
LiftMaster
Model
CAPXS
Equipment type
Smart Video Intercom S, cloud based access control with integrated video camera (controls one door or gate)
Document type
Installation Manual (English, French, and Spanish in one PDF; this page presents the English version)
Manufacturer document number
114-5547-000
Manual revision
Rev A (printed as 114-5547-000 Rev A)
Manual copyright / publication
© 2022 LiftMaster. The manual does not print a separate revision date.
Source
LiftMaster CAPXS Installation Manual; see Original LiftMaster Documentation
HTML resource last updated
November 11, 2026

Common tasks: Set up a myQ Community account | Connect to the internet | Connect power | Wire a door or gate | Reset the CAPXS | Parts and accessories

LiftMaster CAPXS Manual Overview

The LiftMaster CAPXS Smart Video Intercom S (Model CAPXS) is, in LiftMaster's words, a cloud based access control solution that includes an integrated video camera enabling advanced video features. It controls one access point (a door or a gate) through a touchscreen display, microphone, speaker, camera, a primary relay, an auxiliary relay, and Wiegand, request-to-exit, supervised, and postal lock inputs. It connects to the internet by Ethernet or Wi-Fi and is managed through a myQ Community account.

LiftMaster's installation manual is organized in four parts after the introduction: (1) myQ Community account setup, (2) power, (3) network and mounting, and (4) access control. This page follows the same order. The manual covers the CAPXS only; it contains no troubleshooting chart or diagnostic code table, so this page has none either. See Reset Button for the manual's recovery procedure.

CAPXS Connections Overview

The CAPXS has a combination of access control inputs and outputs that work together to control one access point (LiftMaster, page 5).

Swipe sideways to see all columns.

CAPXS inputs and outputs (page 5)
Input / output Terminals Used for
Postal lock input 1, 2 External post lock input.
Wiegand input 3, 4, 5 Standard 26-bit, 30-bit Wiegand, HID 37-bit with Facility Code, Transcore 37-bit, 32-bit MiFare.
Request to exit (REX) and supervised (SUP) input 6, 7, 8 REX: used to request activation/release of the door for exit purposes. SUP: used to monitor the door/gate closed state.
Primary relay output 9, 10, 11 Primary relay for door/gate release.
Auxiliary relay output 12, 13, 14 Auxiliary relay for door/gate release.
Power Power input 16 VDC: (+) red, (-) black, plus ground.
Ethernet Ethernet port Wired network connection (see Connect Internet).

LiftMaster's overview illustration (page 4) labels the display (touchscreen), microphone, speaker, camera window, terminals, power, reset button, Ethernet connection, and postal lock switch. The terminal block is labeled POSTAL LOCK, WIEGAND (BLACK GND, GREEN DATA0, WHITE DATA1), REX / GND / SUP, PRI. RLY. (N.O., COM, N.C.), and AUX. RLY. (N.O., COM, N.C.). Per the manual, only the 26-bit Wiegand protocol is compatible in UL installations. See pages 15 and 16 of the manual for the wiring diagrams, and Door Access and Gate Access below.

What Is in the CAPXS Carton

LiftMaster's carton inventory (page 6) lists these items. The manual notes that the installation manual is provided but not shown.

  • Power supply
  • Ferrite core
  • Torx screw (2)
  • Radio antenna (Security+ 2.0) and cable
  • Installation manual (provided, not shown)

Tools Needed

  • PH2 Phillips screwdriver
  • 1/8 in. flat or PH0 Phillips screwdriver
  • T20 Torx driver/bit

Additional tools LiftMaster recommends: network LAN cable tester, Wi-Fi analyzer app (smartphone app), network analyzer software, a computer with an Ethernet port, and flat head screws for mounting.

Preparation for Installation

LiftMaster recommends downloading and completing its Installation Readiness Survey before installing. Use it to assess the current internet connection details of the community site before a new unit or an upgrade of an installation, and to identify action items needed to proceed. LiftMaster's manual gives this link for the survey: https://p.widencdn.net/oyeejd/114a4574.

All Security Equipment note. The product page for the CAPXS states that every LiftMaster Smart Access Solution requires a monthly myQ Community subscription, that the CAPXS needs a wired internet connection or Wi-Fi to function, and that, because of billing restrictions, it cannot work outside the USA and Canada. See the LiftMaster CAPXS product page for current details.

Source: LiftMaster manual, 114-5547-000 rev a, pages 4 to 6.

Back to contents

LiftMaster CAPXS Specifications

Swipe sideways to see all columns.

CAPXS system specifications as printed by LiftMaster (page 7)
Specification Value
CAPXS capacity Resident capacity 500 / local event history 3,000
CAPXS input voltage 16 VDC +/-10%
Plug-in supply voltage 120 VAC, 60 Hz, 1 AMP, Class 2 output, Level VI efficiency
Operating current 0.5A (typical) at 16VDC
CAPXS operating temperature range -20°C to 50°C (-4°F to 122°F)
Enclosure Polycarbonate
Storage and shipping temperature range -40°C to 85°C (-40°F to 185°F)
Wiegand input (1) 26-bit, *30-bit, *32-bit Mifare, *37-bit with and without facility code, and ASCII (for keypads)
Relay outputs 1 primary and 1 auxiliary relay output, SPDT, rated load 12 VDC, 10 AMP (each)
Accessory compatibility Refer to the accessory page for compatible accessories
Network compatibility 10/100 Ethernet
Wi-Fi compatibility 802.11b/g/n
Wi-Fi security Compatible with routers using WPA3 Personal and WPA2 Personal (AES).
Wi-Fi range Up to 250 feet (76.2 m), open air/line-of-sight to front of panel (range will vary depending on obstructions)
CAPXS video camera** 1080p, viewing angle 135 degree diagonal, up to 1,000 30-second temporary video events stored locally

LiftMaster's notes for this table: *Only the 26-bit Wiegand protocol is compatible in UL installations. Wi-Fi and wireless ranges were not evaluated by UL. **For UL installations, the video camera is for supplement use only.

CAPXS Dimensions

LiftMaster's dimensions drawing (page 7) shows front, side, back, and bottom views with these printed dimensions: 4 in (10.16 cm), 2 in (5.08 cm), 8 in (20.32 cm), 8 in (20.32 cm), and 4 in (10.16 cm). The drawing is not reproduced here; see page 7 of the original manual to match each dimension to its view.

Source: LiftMaster manual, 114-5547-000 rev a, page 7.

Back to contents

Important Safety Information

Safety Warnings From the CAPXS Manual

To reduce the risk of SEVERE INJURY or DEATH:

  • Disconnect power at the fuse box BEFORE proceeding.
  • To AVOID damaging gas, power or other underground utility lines, contact underground utility locating companies BEFORE digging.
  • ALL electrical connections MUST be made by a qualified individual.
  • ALL power and control wiring MUST be run in separate conduit.
  • All power wiring should be on a dedicated circuit and well protected. The location of the power disconnect should be visible and clearly labeled.
  • The CAPXS shall be installed in accordance with the National Electrical Code and all local codes.

To protect against fire and electrocution:

  • Disconnect power BEFORE installing or servicing the CAPXS.
  • NEVER connect a keypad/reader or lock to doors without first consulting the applicable fire code.
  • You MUST consult with, and get approval from, local fire officials BEFORE installing locks or devices on ANY doors that may be fire exits.
  • Use of egress push buttons may not be legal. Single action exits may be required.
  • ALWAYS obtain proper permits and approvals in writing BEFORE installing equipment.

DO NOT INSTALL THE SYSTEM IN THE FAIL SECURE MODE UNLESS PERMITTED BY THE LOCAL AUTHORITY HAVING JURISDICTION. Doing so may cause interference with the operation of panic hardware.

LiftMaster's page 2 also reviews its safety symbols (mechanical and electrical hazards) and signal words, which alert you to the possibility of serious injury or death, or of damage to property or product, if the warnings are not followed. It includes a California Proposition 65 warning: this product can expose you to chemicals including lead, which are known to the State of California to cause cancer or birth defects or other reproductive harm (www.P65Warnings.ca.gov).

All Security Equipment note. Fire exits, egress, and fail-secure installations are governed by local codes and the authority having jurisdiction. Follow the manual and local requirements; this page is not a substitute for them.

Source: LiftMaster manual, 114-5547-000 rev a, page 2.

Back to contents

CAPXS Wire Specifications and Internet Requirements

Wire Specifications

LiftMaster says to use this chart to pull wires in preparation for installation, and to check the national and local building codes BEFORE installation (page 8).

Swipe sideways to see all columns.

CAPXS wire specifications and maximum run distances (page 8)
Description of wire run Wire specification Maximum run distance
Power wire, secondary DC output 2-conductor 14 AWG
2-conductor 16 AWG
2-conductor 18 AWG
Up to 300 feet (91.4 m)
Up to 200 feet (60.9 m)
Up to 100 feet (30.4 m)
Local Area Network (LAN), CAT 5e or better network cable 8-conductor, 24 AWG twisted pair 328 feet* (100 m)
Door strike 2-conductor 18-22 AWG shielded 100 - 250 feet (30.5 - 76.2 m)
Magnetic lock 2-conductor 18-22 AWG 50 - 125 feet (15.2 - 38.1 m)
Dry contact closure (most gate operators) 2-conductor 18-24 AWG shielded 500 - 2500 feet (152.4 - 762 m)
Exit request (REX) 2-conductor 18-24 AWG 500 feet (152.4 m)
Supervised input 2-conductor 18-24 AWG 500 feet (152.4 m)
Wiegand/proximity readers 3-conductor 18-22 AWG shielded 500 feet (152.4 m)

LiftMaster's notes: main power supply and control wiring MUST be run in separate conduits. Conduits must be UL approved for low and high voltage. Refer to the NEC for additional wiring requirements. Category 5e cabling is the minimum performance category recommended. Wiring shall be in accordance with the National Electrical Code (ANSI/NFPA 70), local codes, and authorities having jurisdiction.

Always provide power from a dedicated source. Plug the provided transformer into an outlet wired to its own 10 Amp minimum circuit breaker. This prevents two problems: other equipment cannot introduce spikes, noise, surges, or dips into the power circuit that will affect the system, and the system's operation will not be affected if other equipment develops a short circuit across the power line.

*CAT 5/6 network cable notes: for outdoor distances exceeding 140 feet (42.7 m), a UL497 compliant primary surge protector MUST be installed at the CAPXS. Distances exceeding 328 feet (100 m) may be accommodated with additional hardware (available through third-party sources).

Internet Requirements

When selecting a router, use the following information to ensure compatibility (page 9). The CAPXS can be connected to a router through a wired connection or Wi-Fi. LiftMaster recommends a minimum upload/download speed of 5 Mbps for each CAPXS supporting video camera feeds. This upload speed should be met when considering the use of other devices on the network, like cameras and computers.

  • Wi-Fi security compatibility: WPA3 Personal and WPA2 Personal (AES).
  • Wi-Fi protocols: 802.11b, 802.11g, and 802.11n.
  • Wi-Fi extenders: DO NOT use Wi-Fi extender devices. They may introduce latency in the connection, leading to choppy or lost video transmission.
  • Signal strength: if using a Wi-Fi signal strength tool or app, a continuous Wi-Fi signal strength of at least -65 dBm (numbers closer to zero are stronger) at the CAPXS must be guaranteed to ensure an acceptable connection to the local network. When checking signal strength in CAPXS admin mode, LiftMaster recommends at least two bars, as shown on the CAPXS screen.
  • Hidden networks: hidden network SSIDs are not supported. The network must be selectable from the CAPXS display.
  • Secondary authentication: Wi-Fi networks requiring secondary authentication are not supported (for example, hotel and airport Wi-Fi).

Source: LiftMaster manual, 114-5547-000 rev a, pages 8 and 9.

Back to contents

myQ Community Account Setup

LiftMaster's step 1 (page 10) sets up the myQ Community account and services the CAPXS needs. If you have an existing myQ account, your myQ Community account will have the same password (go to account.myQ.com and log in).

Set Up a myQ Community Account

If you do not have a myQ Community account, LiftMaster gives two methods.

Method 1

  1. Call LiftMaster Customer Care at 800.323.2276 to create a myQ Community account.
  2. You will get a welcome email from LiftMaster. Accept the invitation and register or log in to your account.
  3. Set up the facility, select a subscription plan, add residents, and add credentials (refer to the available Help in myQ Community).
  4. Continue with the installation of the CAPXS in this manual.

Method 2

  1. Navigate to https://www.myqbusiness.com/.
  2. Click the Sign Up button.
  3. Follow the on-screen steps to set up a facility, select Community Manager or Dealer, select a subscription plan, and add residents and credentials.
  4. Continue with the installation of the CAPXS in this manual.

For support, LiftMaster lists 877.247.6764 or support.partner.liftmaster.com/s/community-access-support. VoIP service is required for the calling function: LiftMaster partners exclusively with Phone.com for integrated voice and video calling, and other VoIP providers are not compatible with the CAPXS.

Sign Up for myQ Community Services

Service subscriptions are required for the CAPXS to fully function. To sign up for services:

  1. Set up a myQ Community account. Go to account.myQ.com. If you do not have a myQ account, choose Sign Up and follow the prompts. If you have an existing myQ account, choose Log In.
  2. Create a new community. If you do not have any communities in your account, you will be prompted to create one. Follow the prompts to complete the community creation.
  3. Add devices and a subscription plan. Under Device Management, select the CAPXS and any other LiftMaster access control devices. The subscription plan is pre-selected based on the selected devices. Select any add-on services and check out. Follow the prompts to finish adding the CAPXS and any other LiftMaster access control devices.
  4. Configure the community. Under People, People Management, add residents, and make sure to assign at least one access group to each resident. Under People, Mobile App License Management, assign myQ Community app licenses to residents. For more, LiftMaster refers to its admin and community manager support pages.
  5. Continue with the installation of the CAPXS in this manual.

Source: LiftMaster manual, 114-5547-000 rev a, page 10.

Back to contents

LiftMaster CAPXS Installation

LiftMaster's installation steps are: Step 1, install the mounting bracket; Step 2, connect power; Step 3, connect internet; Step 4, set up the CAPXS; Step 5, mount the CAPXS; and then wire the door or gate access.

Install the Mounting Bracket (Step 1)

Step 1, install the mounting bracket

  1. Mount the CAPXS mounting bracket securely to a flat surface or pedestal with appropriate 1/4 in. flat head hardware for a surface mount, or the appropriate #6 flat head screw for a gang box mount. Stainless steel hardware is recommended for mounting.
  • ADA compliance: when mounting the CAPXS at a pedestrian entrance, to meet ADA compliance, mount the top of the CAPXS screen no higher than 54 inches from the ground.
  • Sealing: make sure the CAPXS is properly sealed to prevent damage from moisture. For rough surfaces such as brick, additional sealing will be needed.

LiftMaster's illustrations show a surface mount and a gang box mount.

Source: LiftMaster manual, 114-5547-000 rev a, page 11.

Back to contents

Connect Power (Step 2)

  • DO NOT use ANY power supply other than those supplied with your CAPXS.
  • DO NOT power electronic strikes and latches with the same power supply used to power the access control panel; doing so will cause DAMAGE to the CAPXS. Use ONLY a UL listed burglar alarm or access control system to power electronic strikes and latches.
  • DO NOT connect the power supply to a switched outlet or otherwise controlled AC outlet.
  • DO NOT connect the power supply to the 120 Vac outlet until ALL wiring is completed.
  • DISCONNECT the power supply from the 120 Vac outlet prior to inserting or removing wires from the terminal block to the control board.

The outlet for the CAPXS MUST be an external dedicated 120 Vac outlet, wired back to its own 10 Amp minimum circuit breaker. Maximum wire run distances for the power wiring:

Swipe sideways to see all columns.

CAPXS power wire run (page 12)
Wire specification Maximum run distance
14 AWG Up to 300 feet (91.4 m)
16 AWG Up to 200 feet (60.9 m)
18 AWG Up to 100 feet (30.4 m)

Step 2, connect power

  1. Connect 14-18 AWG wire to the screw terminals on the power supply. Use 2-conductor, red/black, jacketed wire. Use red for + and black for -.
  2. While pushing down the orange tab on the CAPXS power input connector on the control board, insert the stripped wire into the respective polarity input.
  3. Release the orange tab on the power input connector to lock the wire in place.
  4. Plug the power supply into a 120 Vac outlet after all connections have been made.

Note: green LEDs on the control board will light when powered up. The CAPXS will display a myQ logo while booting up. When boot up is complete, the user interface will appear.

  • If the power supply is installed outdoors, the power supply must have its own approved NEMA 4 rated weatherproof electrical enclosure. Use conduit from the power supply enclosure to the controller enclosure.
  • When the power supply (low voltage) wiring leaves the enclosure, the wire must be rated for wet and damp locations.
  • High voltage wiring must be run in a separate conduit from low voltage wiring.

Source: LiftMaster manual, 114-5547-000 rev a, page 12.

Back to contents

Connect Internet (Step 3)

The CAPXS can connect to the internet with a wired connection or with Wi-Fi (wireless); see Internet Requirements. If you are not in Admin Mode, press the 3 dots in the upper right corner of the CAPXS display and enter the Admin Code, press the Network tab on the display, and press the "Change Network Settings" button. Follow the instructions for your application.

Note: the default Admin Code can be found in your myQ Business account. When you add a CAPXS device to a facility, you will be prompted to create a new Admin Code.

Option 1, wired connection

The Local Area Network (LAN) port is a 10/100 Ethernet interface with an RJ45 jack for connecting the CAPXS to a hub, switch, or router so it can gain internet connectivity. Use a straight (non-crossover) Cat5e or Cat6 cable, referred to as an Ethernet cable in the manual.

  1. Connect an Ethernet cable from the hub, switch, or router to the LAN port on the back of the CAPXS. When connected properly, the green and amber LEDs on the Ethernet port on the back of the CAPXS will light or flicker. If the green LED is not lit, check the connections on the CAPXS and the Ethernet hub.
  2. On the display, select Wired Network if dynamic configuration (DHCP) is desired, or select Manual Setup for a static IP address.

Option 2, connect through Wi-Fi (wireless)

  1. On the display, select Wi-Fi Network.
  2. Select the network the CAPXS will use.
  3. Enter the password for the network.
  4. Select Login.

Additional compatibility considerations (LiftMaster): when checking signal strength in CAPXS admin mode, LiftMaster recommends at least two bars. If using a Wi-Fi signal strength tool or app, a continuous signal strength of at least -65 dBm at the CAPXS must be guaranteed. Hidden network SSIDs are not supported, and Wi-Fi networks requiring secondary authentication (such as hotel and airport Wi-Fi) are not supported.

LiftMaster's illustration labels the Ethernet path (router/switch, modem, Ethernet cable, 325 feet [99.1 m] maximum) and a Wi-Fi signal graphic with three ranges: -30 to -67 dBm GOOD, -66 to -85 dBm POSSIBLE, and -86 dBm or weaker POOR.

Documentation note. The manual gives two different maximum Ethernet cable lengths: 328 feet (100 m) in the wire specifications and cable notes (page 8) and 325 feet (99.1 m) in the Connect Internet illustration (page 13). Also, the text requires a continuous signal of at least -65 dBm (pages 9 and 13), while the signal graphic shows GOOD as -30 to -67 dBm and POSSIBLE as -66 to -85 dBm (page 13). Treat the stronger requirement as the safer target and confirm with LiftMaster if your installation is near these limits.

Source: LiftMaster manual, 114-5547-000 rev a, page 13.

Back to contents

Set Up the CAPXS (Step 4)

On the display, select each tab in Admin Mode to validate the setup (network, inputs, outputs, and so on). Once you have validated the setup, exit Admin Mode.

Mount the CAPXS (Step 5)

Insert the CAPXS into the mounting bracket until the unit snaps into place. Using the screws provided, tighten the screws through the side of the mounting bracket to securely affix the CAPXS to the mounting bracket.

All Security Equipment note. In LiftMaster's English text, the Step 4 and Step 5 headings appear after their paragraphs, so this page assigns the Admin Mode validation paragraph to Step 4 and the bracket insertion paragraph to Step 5, which matches the order of the manual's table of contents (Setup CAPXS, then Mounting CAPXS). Check page 14 of the original manual if the order matters for your installation.

Source: LiftMaster manual, 114-5547-000 rev a, page 14.

Back to contents

CAPXS Access Control Wiring

LiftMaster's manual shows two example wiring setups: door access (page 15) and gate access (page 16). Both say to disconnect power BEFORE making electrical connections. The diagrams are not reproduced on this page; use the original manual pages for terminal-level connections, and the notes below, which LiftMaster prints on the diagrams.

  • Disconnect power BEFORE making electrical connections.
  • DO NOT connect high voltage power to the CAPXS unit.
  • DO NOT INSTALL THE SYSTEM IN THE FAIL SECURE MODE UNLESS PERMITTED BY THE LOCAL AUTHORITY HAVING JURISDICTION. Doing so may cause interference with the operation of panic hardware.

Door Access (Page 15)

The labels on LiftMaster's door access example include: push button, door strike, maglock, proximity sensor, request to exit (REX), supervised (door status) with a supervised or non-supervised door sensor, Wiegand reader or keypad (DATA0 green, DATA1 white, ground, power), postal lock, primary relay, auxiliary relay (alarm bypass and a light), Ethernet connection, and power. The diagram itself is the authority for which device connects to which terminal.

  • Maglock and door strike power: use a separate power supply (not provided). DO NOT use the controller's power supply for the maglock or the door strike. Use 18-22 AWG wire.
  • Surge protection for the lock: for DC power, install a 1N4005 diode or equivalent. For AC power, install a Siemens S10K30MOV (metal oxide varistor) or equivalent.
  • Supervised input: the diagram shows an end-of-line (EOL) resistor (1k ohm) with a supervised or non-supervised door sensor.
  • Wiegand device wiring: keep the length of unshielded wires to a minimum to avoid electrical noise. For a KPR2000 keypad, wire the pink and black (ground) wires together.
  • Light or load on the auxiliary relay: the diagram's labels include an isolation relay, a low voltage power supply, and the load, line, and neutral connections.
  • UL evaluation: the maglock, door strike, and alarm bypass were not evaluated by UL.
  • Postal lock: for more information on wiring a postal lock, refer to the manual for accessory CAPXSTKPL.

Source: LiftMaster manual, 114-5547-000 rev a, page 15.

Back to contents

Gate Access, Wired (Page 16)

The labels on LiftMaster's gate access example include: push button, request to exit, external free exit loop detector, maglock, gate operator, supervised (gate status), Wiegand reader or keypad, postal lock, primary relay, auxiliary relay (alarm bypass and a light), Ethernet connection, and power. The diagram itself is the authority for which device connects to which terminal.

  • Gate operator connection: connect the supervised input to the gate operator's auxiliary closed limit switch; refer to the gate operator manual. The supervised (gate status) input is not applicable for wireless gate operator connections.
  • Maglock: use 18-22 AWG wire and a separate power supply (not provided). DO NOT use the controller's power supply. For DC power, install a 1N4005 diode or equivalent. For AC power, install a Siemens S10K30MOV (metal oxide varistor) or equivalent.
  • Wiegand device wiring: for a KPR2000 keypad, wire the pink and black (ground) wires together.
  • UL evaluation: the maglock and alarm bypass were not evaluated by UL.
  • Postal lock: for more information, refer to the manual for accessory CAPXSTKPL.

For gate operator terminal names and limit switch wiring, see the operator pages on this site (for example the gate operators collection) and the manual for your operator.

Source: LiftMaster manual, 114-5547-000 rev a, page 16.

Back to contents

CAPXS Reset Button

LiftMaster recommends resetting the CAPXS to factory defaults by using the Factory Reset option in Admin Mode. If you have forgotten the Admin Code, or the display has become unresponsive, you can manually reset the CAPXS using the reset button.

To manually reset the CAPXS

  1. With the CAPXS powered on, press and hold the reset button for 3 seconds.
  2. The CAPXS will reboot and restore factory default settings.

Note: resetting to factory default settings will erase network settings. Have the network configuration information available to re-enter once the reset completes.

Source: LiftMaster manual, 114-5547-000 rev a, page 17.

Back to contents

CAPXS Repair Parts and Accessories

LiftMaster's page 18 lists two tables under the headings "Repair Parts" and "Accessories." The links below open related All Security Equipment category pages and do not by themselves confirm that we stock an item or that it fits your CAPXS.

Repair Parts

Swipe sideways to see all columns.

CAPXS repair parts as printed by LiftMaster (page 18)
Item Part number
Mounting bracket, CAPXS K41-0273-000
Power supply kit K041-0353-000

Compatible CAPXS Accessories

Swipe sideways to see all columns.

CAPXS accessories as printed by LiftMaster (page 18)
Item Part number
Reader, multi-class SE RP10 mini mullion LMMC-MINI
CAPXS hood (ideal for overly bright applications) CAPXSHOOD
CAPXS trim kit with postal lock CAPXSTKPL
CAPXS trim kit without postal lock CAPXSTK
Wiegand keypad/proximity reader KPR2000*
Connected Access Portal, 2 door CAP2D

*The KPR2000 is not UL listed to UL 294. It cannot be used as the primary means of granting or denying access, only for supplemental use. LiftMaster also notes that a current list of compatible readers and keypads is maintained at LiftMaster.com; if your reader or keypad model is not listed there, contact LiftMaster Technical Support to determine compatibility.

Shop related products: intercom and telephone entry systems | keypads | fob and card readers | access control accessories | power supplies

Documentation note. In the English text of page 18, the heading "Accessories" appears first and the heading "Repair Parts" after both tables, while the table of contents lists Repair Parts before Accessories. This page assigns the mounting bracket and power supply kit to Repair Parts and the readers, hood, trim kits, keypad, and CAP2D to Accessories based on their content. Confirm against page 18 of the original manual.

Source: LiftMaster manual, 114-5547-000 rev a, page 18.

Back to contents

CAPXS Configuration Sheet

LiftMaster provides a configuration sheet (page 19) to record device information and configuration settings. It has fields for the CAPXS name; notes; the door/gate name for Door 1; the inputs (Wiegand, REX, status/SUP, and whether an EOL resistor is used, yes or no); and the outputs (primary relay and auxiliary relay, each normally open or normally closed). LiftMaster notes that any user of the system is subject to the terms outlined in the product EULA. Print the sheet from the original manual to fill it in.

Source: LiftMaster manual, 114-5547-000 rev a, page 19.

Back to contents

The manual's legal page (page 20) includes the following topics. It is summarized here; read the original page for the full text.

  • Canada, Underwriters Laboratories: the CAPXS shall be installed in accordance with Part 1 of the Canadian Electrical Code.
  • Documentation disclaimer: information in the manual is subject to change without notice and does not represent a commitment on the part of LiftMaster; LiftMaster directs readers to LiftMaster.com for the most up-to-date information. The document and its data shall not be duplicated, used, or disclosed to others for procurement or manufacturing except with LiftMaster's written permission.
  • UL 294 ratings printed: Endurance: Level 4, Line security: Level 1, Destructive Attack: Level 1, Power Standby: Level 1.
  • FCC and Innovation, Science and Economic Development Canada: the device complies with part 15 of the FCC rules and Canadian license-exempt RSS standards, and is a Class B digital device. Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. The device must be installed to maintain a minimum 20 cm (8 in.) distance between users or bystanders and the device. The transmitter must not be co-located or operated with any other antenna or transmitter. Frequency tolerance is +/-20 p.p.m. To access device compliance information for FCC and IC, tap the "i" in the upper left corner of the CAPXS home screen.
  • ADA: when mounting the CAPXS at a pedestrian entrance, mount the top of the screen no higher than 54 inches from the ground.
  • Local requirements: refer to the local jurisdiction for any specific requirements, such as physical signage that may be required.

Source: LiftMaster manual, 114-5547-000 rev a, page 20.

Back to contents

CAPXS Warranty

Per LiftMaster's warranty (page 21), LiftMaster ("Seller") warrants to the first purchaser of the product, for the structure in which it is originally installed, that it is free from defects in materials and workmanship for a period of two years from the date of purchase. Proper operation depends on complying with the instructions for installation, operation, maintenance, and testing; failure to comply strictly with those instructions will void the limited warranty in its entirety.

If, during the warranty period, the product appears to contain a covered defect, LiftMaster says to call 1-800-528-2806 before dismantling the product, then send it, pre-paid and insured, to its service center for warranty replacement. The warranty does not cover non-defect damage, damage caused by improper installation, operation, or care, labor charges for reinstalling a repaired or replaced unit, problems related to interference, or replacement of batteries, and it limits liability as stated in the full text. The complete terms are printed on page 21 of the manual.

All Security Equipment note. If you bought your CAPXS from All Security Equipment, see our refund policy and our Help Center for how manufacturer warranty returns are handled.

Source: LiftMaster manual, 114-5547-000 rev a, page 21.

Back to contents

Frequently Asked Questions About the LiftMaster CAPXS

How many doors or gates can one CAPXS control?

One. The manual describes a combination of inputs and outputs that work together to control one access point (page 5). For more entries, LiftMaster's other Smart Video Intercom models and the CAP2D two-door controller are options; see Related LiftMaster Resources.

What does the CAPXS need to work?

Per the manual: a myQ Community account with a service subscription (page 10), a dedicated 120 Vac outlet and the supplied power supply (page 12), an internet connection by Ethernet or Wi-Fi with at least 5 Mbps upload and download per CAPXS that supports video (page 9), and VoIP service through Phone.com for the calling function (page 10).

What Wi-Fi does the CAPXS support?

802.11b/g/n with WPA3 Personal or WPA2 Personal (AES), up to 250 feet open air. It does not support Wi-Fi extenders, hidden SSIDs, or networks that require secondary authentication such as hotel or airport Wi-Fi (pages 7 and 9). See Internet Requirements.

How far can I run the power wire?

Up to 300 feet with 14 AWG, 200 feet with 16 AWG, and 100 feet with 18 AWG (page 12). See Connect Power.

Where do I find the Admin Code?

The default Admin Code can be found in your myQ Business account. When you add a CAPXS device to a facility, you are prompted to create a new Admin Code (page 13).

How do I reset the CAPXS?

Use the Factory Reset option in Admin Mode. If you have forgotten the Admin Code or the display is unresponsive, press and hold the reset button for 3 seconds with the unit powered on. This erases network settings (page 17). See Reset Button.

Which Wiegand formats does the CAPXS accept?

26-bit, 30-bit, 32-bit MiFare, and 37-bit with and without facility code, plus ASCII for keypads; only the 26-bit protocol is compatible in UL installations (pages 5 and 7).

How high should I mount the CAPXS?

At a pedestrian entrance, to meet ADA compliance, mount the top of the screen no higher than 54 inches from the ground (page 11). See Install the Mounting Bracket.

Can I power a maglock or door strike from the CAPXS power supply?

No. LiftMaster says not to use the controller's power supply for the maglock or door strike, and to use only a UL listed burglar alarm or access control system to power electronic strikes and latches (pages 12, 15, and 16).

What warranty does the CAPXS have?

LiftMaster's limited warranty is two years from the date of purchase. See CAPXS Warranty and page 21 of the manual.

Does the manual come in other languages?

Yes. LiftMaster's combined PDF has the English manual on pages 1 to 21, French on pages 22 to 42, and Spanish on pages 43 to 63. This page presents the English version.

Original LiftMaster CAPXS Documentation

This HTML resource is presented by All Security Equipment, is not a LiftMaster publication, and does not replace the original manufacturer documentation. It is based on LiftMaster's CAPXS Smart Video Intercom S installation manual, document 114-5547-000, Rev A (© 2022 LiftMaster).

Check LiftMaster's product page for the current revision before relying on any document, because LiftMaster may update them.

Other LiftMaster manuals on this site: CSL24UL | SL3000UL | LA500 | CSW24UL | RSW12UL

Need the intercom itself? All Security Equipment sells the LiftMaster CAPXS Smart Video Intercom S for single-family homes and small buildings.

This resource was last updated November 11, 2026. Based on LiftMaster document 114-5547-000 Rev A.