LiftMaster CAPXLV2 Smart Video Intercom L, a cloud based access control video intercom with touchscreen display and camera
LiftMaster CAPXLV2 Smart Video Intercom L. Product image from All Security Equipment.

Documentation Information

Manufacturer
LiftMaster (Chamberlain Group, LLC)
Model
CAPXLV2
Equipment type
Smart Video Intercom L, cloud based access control with integrated video camera (up to 8 access points)
Document type
Installation Manual (English, French, and Spanish in one PDF; this page presents the English version, pages 1 to 28)
Manufacturer document number
114-5891-000
Manual revision
Rev. E (printed as 114-5891-000 (Rev. E))
Manual copyright / publication
©2025 Chamberlain Group, LLC. The manual does not print a separate revision date.
Source
LiftMaster CAPXLV2 Installation Manual; see Original LiftMaster Documentation
HTML resource last updated
November 11, 2026

Common tasks: Set up a myQ Community account | Connect to the internet | Connect power | Wire a door or gate | Pair a gate operator | Parts and accessories

LiftMaster CAPXLV2 Manual Overview

The LiftMaster CAPXLV2 Smart Video Intercom L (Model CAPXLV2, branded "myQ Community Smart Video Intercom L" on the manual's cover) is a cloud based access control intercom with a touchscreen display, camera, speaker, microphone, and proximity reader area. It has a main board and one or two door of control boards, and the manual says it can control up to 8 access points in total (up to 4 per door of control board). It supports Wiegand readers, OSDP readers, a built-in Security+ 2.0 receiver for wireless gate operator pairing, Wi-Fi, Bluetooth mobile credentials, and 24 V or PoE power.

LiftMaster's manual is organized in four parts after the introduction: (1) pre-install (myQ Community account and services), (2) install (knockouts, mounting, antennas, ground, power), (3) network, and (4) access control (gate and door wiring, readers, Wiegand output, postal lock, wiring diagram, parts, accessories). This page follows the same order. The manual has no troubleshooting chart or diagnostic code table, so this page has none either.

LiftMaster warning (page 2): this product is not user serviceable. This product shall only be installed and maintained by a professional installer.

Main Board Overview

LiftMaster's main board overview (page 5) lists these inputs and outputs. Its illustration of the board is not reproduced here.

Swipe sideways to see all columns.

CAPXLV2 main board inputs and outputs (page 5)
Input / output Used for
Power In Connect to external 24v power supply.
Ethernet/PoE Connect an Ethernet switch or router for 10/100BaseT, or a PoE injector for PoE power via RJ45.
USB1, USB2 Reserved for future use.
DOC 1, DOC 2 Connect to door of control board 1 and door of control board 2.
OSDP Connect an RS-485 bus that can connect up to 4 OSDP readers in a daisy chain within 1000 ft and provide 12v power to the connected OSDP readers.
Postal Lock Connect to the postal lock.
SPKR Connect to the built-in speaker.
WiFi Antenna Connect to an external WiFi antenna.
USB Camera Connect to the built-in camera.
Status LED Display power diagnostics status: DIAG, +3.3v, +5v, +12v.
Radio Antenna Connect to an external radio antenna for Security+ 2.0.
DIAG For internal use only.
MIC Connect to the built-in microphone.

The illustration also labels the external RF cable bracket and a learn button on the edge of the vertical board.

Door of Control Board Overview

The CAPXLV2 has a combination of access control inputs and outputs on the door of control board(s) that work together to control up to 4 access points each, so the CAPXLV2 can control up to 8 access points in total (page 6). The ports are configurable.

Swipe sideways to see all columns.

CAPXLV2 door of control board inputs and outputs (page 6)
Input / output type (configurable) Used for
Monitored inputs: REX (request to exit) External free exit loop detectors, REX buttons, and proximity sensors.
Monitored inputs: Knox box In the case of an emergency (medical or fire), the Fire Rescue Department is able to gain entry.
Monitored inputs: Status Door sensors detecting when a door is ajar; supervised gate operators detecting when they failed to close; supervised gate operators detecting when they failed to open.
Relay Gate operator, door strikes, alarm shunt, maglocks, and lights (for control only; power to be provided by an external supply).
Wiegand input Proximity readers (Wiegand 12Vdc power is for readers only; do not use it to power other external devices).
Wiegand output Access grant activity for integration with other access systems.

Each door of control board has monitored inputs (1 to 4 on the first board and 5 to 8 on the second), relays (1 to 4 and 5 to 8), and Wiegand ports (1 and 2, and 3 and 4), plus a Wiegand output; one Wiegand output is labeled "for internal use only. Do not connect." Monitored inputs can operate as REX, Knox box, or status. Per the manual, only the 26-bit Wiegand protocol and OSDP protocol are compatible in UL installations, and the Wiegand 12V power output port must not power anything except the Wiegand proximity readers.

CAPXLV2 Overview Illustration

LiftMaster's overview illustration (page 4) labels the front panel lock, microphone port, speaker port, postal lock location, proximity reader, touchscreen display, camera window, door control board 1 and 2, postal lock (if installed), speaker, camera, main board, and microphone.

What Is in the CAPXLV2 Carton

LiftMaster's carton inventory (page 7) lists these items: power supply (K41-0227-000), S10K30MOV metal oxide varistors (8), 1N4005 diode kit (8), 100 ohm 1/4 watt resistors (2), and rubber washers (4). Page 13 also says the Security+ 2.0 radio antenna (if applicable) is included in the package.

Tools Needed

  • PH2 Phillips screwdriver
  • Precision 1/8 in. flat or PH0 Phillips screwdriver
  • 1/4 in. nut driver
  • Drill/driver and 7/64 in. drill bit
  • Hammer drill bits for the drill/driver
  • RJ45 crimping pliers
  • Multimeter and measuring tape
  • Conduit bender and conduit cutter/reamer
  • Hack saw
  • Center punch tool and hammer

Additional tools LiftMaster recommends: network LAN cable tester, Wi-Fi analyzer app (smartphone app), network analyzer software, a computer with an Ethernet port, and flat head screws for mounting.

Prepare for Installation

LiftMaster recommends downloading and completing its Installation Readiness Survey before installing. Use it to assess the current internet connection details of the community site before a new unit or an upgrade of an installation, and to identify action items needed to proceed. LiftMaster's manual gives this link: https://p.widencdn.net/oyeejd/114a4574.

All Security Equipment note. The product page for the CAPXLV2 states that every LiftMaster Smart Access Solution requires a monthly myQ Community subscription, that the CAPXLV2 needs a wired internet connection or Wi-Fi to function, and that, because of billing restrictions, it cannot work outside the USA and Canada. See the LiftMaster CAPXLV2 product page for current details.

Source: LiftMaster manual, 114-5891-000 Rev. E, pages 2 to 7.

Back to contents

LiftMaster CAPXLV2 Specifications

Swipe sideways to see all columns.

CAPXLV2 system specifications as printed by LiftMaster (page 8)
Specification Value
Compliance UL294
CAPXLV2 capacity Resident capacity 50,000 / local event history 50,000
Supply voltage 1 (VIN connector) 24V DC 72W (3A) MAX. The 24v power supply provided in the box is recommended.
Supply voltage 3 (AC/DC converter) 120 VAC, 1.5 A, 60 Hz
Supply voltage 2 (PoE) 42-55VDC 802.3BT Type 3 Class 5 or Class 6
PoE supply connector configuration Alternative B (or Mode B)
Operating temperature -20-50C
Operating humidity range 20% to 85 +/-5% RH
Storage and shipping temperature -40-85C
Enclosure Front (aluminum), rear (carbon steel)
Wiegand inputs* (4) 26-bit, *30-bit, *32-bit Mifare, *36-bit Mifare, *56-bit Mifare, *37-bit with and without facility code, and ASCII (for keypads). 12VDC, 250mA power output (per input)
Relay contacts (8) SPDT 3A @ 30VDC (each)
OSDP OSDP 2.2, 12 Vdc, 1.3 A max (total). OSDP interface (1): connect up to 4 recommended OSDP readers in a daisy chain configuration. LiftMaster is working to optimize the product to support up to 8 OSDP readers in a future firmware release; check the firmware release notes.
Accessory compatibility Refer to the accessory page for compatible accessories
Network compatibility 10/100 Ethernet
Bluetooth Version 5.0
Wi-Fi compatibility 802.11 a/b/g/n and 802.11ac, 2.4GHz / 5GHz
Wi-Fi security Compatible with routers using WPA3-SAE, WPA2-PSK/WPA3-SAE, WPA2-PSK, or WPA/WPA2-PSK
Wi-Fi range (with external antenna) Up to 500 feet (152.4 m), open air/line-of-sight (range will vary depending on obstructions and 2.4GHz/5GHz router type)
Mobile credentials Minimum configuration: Bluetooth technology employing myQ Community app version 3.4.0 or above. The smart phone must have these minimum operating system versions: iOS 15, 16 or 17, Android 7 (Nougat) to Android 13. Access to the wireless electronic device (smartphone, tablet, etc.) must be secured by either a PIN password or biometric feature. When a mobile device is used to gain access, the credential is identified as "mobile" in the associated myQ Community "credential type" field.
Built-in LiftMaster Passport receiver Security+ 2.0
Wireless communication to gate operator Up to 750 feet (228.6 m), open air/line-of-sight (range will vary depending on obstructions). Compatible with LiftMaster Security+ 2.0 gate operators, 2018 LiftMaster gate operators (firmware v4.4 and later), and HD operators (firmware v3.3 or later). NOT compatible with LiftMaster barrier gate operators.
Video camera 1080p, viewing angle 135 degree diagonal, up to 1,000 30-second temporary video events stored locally

LiftMaster's notes: *Only the 26-bit Wiegand protocol and OSDP protocol are compatible in UL installations. Wi-Fi is supplemental for UL installations. Supply voltage 1: for UL installations, use only an ITE Listed, power limited power supply manufactured by Shenzhen Geao technology Co. Ltd, model QX72W240300D3. Supply voltage 2: for UL installations, it must be connected to a UL 294 or UL 603 listed power supply or a UL 294 PoE injector with 0 hours (minutes) battery back-up.

Documentation note. The OSDP specification, the main board overview, and the specifications all describe up to 4 OSDP readers, but the wire specification chart (page 9) says "Recommended OSDP reader (up to 8 units daisy chained)." The English specification also gives the PoE input as 42-55VDC, while the French and Spanish versions of the same manual print 42-57 (and the French power page prints 42-57 Vdc in one place and 42-55 Vdc in another). Confirm with LiftMaster before sizing a PoE injector or an OSDP chain at the limit.

CAPXLV2 Dimensions

LiftMaster's dimensions drawing (page 8) shows front, side, back, and bottom views. The drawing and its dimension labels are not reproduced here; see page 8 of the original manual.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 8.

Back to contents

Important Safety Information

Safety Warnings From the CAPXLV2 Manual

To reduce the risk of SEVERE INJURY or DEATH:

  • Disconnect power at the fuse box BEFORE proceeding.
  • To AVOID damaging gas, power or other underground utility lines, contact underground utility locating companies BEFORE digging.
  • ALL electrical connections MUST be made by a qualified individual.
  • ALL power and control wiring MUST be run in separate conduit.

To protect against fire and electrocution:

  • Disconnect power BEFORE installing or servicing the CAPXLV2.
  • NEVER connect a keypad/reader or lock to doors without first consulting the applicable fire code.
  • You MUST consult with, and get approval from, local fire officials BEFORE installing locks or devices on ANY doors that may be fire exits.
  • Use of egress push buttons may not be legal. Single action exits may be required.
  • ALWAYS obtain proper permits and approvals in writing BEFORE installing equipment.
  • ALWAYS ensure that the CAPXLV2 front lid is locked properly using the provided key after any servicing or maintenance of the product is complete and before operating the product.
  • NEVER leave any exposed wiring inside the cabinet.

WARNING: this product is not user serviceable. This product shall only be installed and maintained by a professional installer.

LiftMaster's page 2 also reviews its safety symbols (mechanical and electrical hazards) and signal words, which alert you to the possibility of serious injury or death, or of damage to property or product, if the warnings are not followed. (The French and Spanish pages of the manual also print a California Proposition 65 warning; the English page 2 does not.)

All Security Equipment note. Fire exits, egress, and locking devices are governed by local codes and the authority having jurisdiction. Follow the manual and local requirements; this page is not a substitute for them.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 2.

Back to contents

CAPXLV2 Wire Specifications

LiftMaster says to use this chart to pull wires in preparation for installation, and to check the national and local building codes BEFORE installation (page 9).

Swipe sideways to see all columns.

CAPXLV2 wire specifications and maximum run distances (page 9)
Description of wire run Wire specification Maximum run distance
Recommended OSDP reader (up to 8 units daisy chained, as printed) 22 AWG, 2 twisted pairs (4 conductor): one pair for PWR/GND and one pair for D0/D1. Shielded cable is optional, terminated with 100 ohms at each end. 1000 feet (304.8 m)
Power wire, 24V DC power supply 2-conductor 14 AWG
2-conductor 16 AWG
2-conductor 18 AWG
Up to 300 feet (91.4 m)
Up to 200 feet (60.9 m)
Up to 100 feet (30.4 m)
Local Area Network (LAN), CAT 5e or better network cable (also for PoE setup) 8-conductor, 24 AWG twisted pair 328 feet* (100 m)
Grounding the chassis (use grounding lug in the CAPXLV2) 12 AWG copper 12 feet (3.7 m)
Door strike 2-conductor 18-22 AWG shielded 100 - 250 feet (30.5 - 76.2 m)
Magnetic lock 2-conductor 18-22 AWG 50 - 125 feet (15.2 - 38.1 m)
Dry contact closure (most gate operators) 2-conductor 18-24 AWG shielded 500 - 2500 feet (152.4 - 762 m)
Exit request (REX) 2-conductor 18-24 AWG 500 feet (152.4 m)
Supervised input 2-conductor 18-24 AWG 500 feet (152.4 m)
Wiegand/proximity readers 7-conductor 18-22 AWG shielded 500 feet (152.4 m)
Postal lock box 2-conductor 18-24 AWG 250 - 1000 feet (76.2 - 304.8 m)

LiftMaster's notes: main power supply and control wiring MUST be run in separate conduits. Conduits must be UL approved for low and high voltage. Refer to the NEC for additional wiring requirements. Category 5e cabling is the minimum performance category recommended. Wiring shall be in accordance with the National Electrical Code (ANSI/NFPA 70), local codes, and authorities having jurisdiction.

Always provide power from a dedicated source. Plug the provided transformer into an outlet wired to its own 10 Amp minimum circuit breaker. This prevents two problems: other equipment cannot introduce spikes, noise, surges, or dips into the power circuit that will affect the system, and the system's operation will not be affected if other equipment develops a short circuit across the power line.

Postal lock notes: the postal lock cable length shall not exceed 98.5 ft (30 m) for UL 294 compliance.

*CAT 5e/6 network cable notes: for outdoor distances exceeding 140 feet (42.7 m), a UL497 compliant primary surge protector MUST be installed at the CAPXLV2. Distances exceeding 328 feet (100 m) may be accommodated with additional hardware (available through third-party sources).

Documentation note. The wire specification chart gives the postal lock box run as 250 - 1000 feet (76.2 - 304.8 m), while its own postal lock note, and page 23, limit the postal lock cable to 98.5 ft (30 m) for UL 294 compliance. Use the shorter limit for UL 294 installations.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 9.

Back to contents

myQ Community Account Setup

LiftMaster's pre-install step (page 10) sets up the account and services the CAPXLV2 needs. The services listed are required for the CAPXLV2 to fully function. If you have an existing myQ account, your myQ Community account will have the same password (go to account.myQ.com and log in).

Set Up a myQ Community Account

Method 1

  1. Call LiftMaster Customer Care at 877.247.6764 to create a myQ Community account.
  2. You will get a welcome email from LiftMaster. Accept the invitation and register or log in to your account.
  3. Set up the facility, select a subscription plan, add residents, and add credentials (refer to the available Help in myQ Community).
  4. Continue with the installation of the CAPXLV2 in this manual.

Method 2

  1. Navigate to account.myq.com.
  2. Click the Sign Up button.
  3. Follow the on-screen steps to set up a facility, select Community Manager or Dealer, select a subscription plan, and add residents and credentials.
  4. Continue with the installation of the CAPXLV2 in this manual.

Sign Up for myQ Community Services

Service subscriptions are required for the CAPXLV2 to fully function. To sign up for services:

  1. Set up a myQ Community account. Go to account.myQ.com. If you do not have a myQ account, choose Sign Up and follow the prompts. If you have an existing myQ account, choose Log In.
  2. Create a new community. If you do not have any communities in your account, you will be prompted to create one. Follow the prompts to complete the community creation.
  3. Add devices and a subscription plan. Under Device Management, select the CAPXLV2 and any other LiftMaster access control devices. The subscription plan is pre-selected based on the selected devices. Select any add-on services and check out. Follow the prompts to finish adding the CAPXLV2 and any other LiftMaster access control devices.
  4. Configure the community. Under People, People Management, add residents, and make sure to assign at least one access group to each resident. Under People, Mobile App License Management, assign myQ Community app licenses to residents. For more, LiftMaster refers to its admin and community manager support pages.
  5. Continue with the installation of the CAPXLV2 in this manual.

For support, LiftMaster lists 877.247.6764 or support.partner.liftmaster.com/s/community-access-support. VoIP service is required for the calling function: LiftMaster partners exclusively with Phone.com for integrated voice and video calling, and other VoIP providers are not compatible with the CAPXLV2.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 10.

Back to contents

LiftMaster CAPXLV2 Installation

LiftMaster's installation steps are: Step 1, remove knockouts; Step 2, mount the CAPXLV2; Step 3, install antennas; Step 4, ground the unit; Step 5, connect power. Network setup then follows (connect internet and validate setup), and then the access control wiring.

Remove Knockouts (Step 1)

To prevent damage to the CAPXLV2 from moisture or water:

  • DO NOT install during rain. Internal components MUST be kept free of water and moisture.
  • BEFORE opening the front cover of the CAPXLV2, remove ANY accumulated water from the top of the CAPXLV2.

To prevent damage to ANY internal components:

  • DO NOT attempt to remove the knockouts with a hammer. Banging on the knockouts may result in shock to the circuit boards, which could cause permanent damage.
  • Some internal wires may be close to the knockouts. Make sure to move any wire away from the knockouts.

Step 1, remove knockouts

  1. Turn the key clockwise to unlock the CAPXLV2.
  2. Open the door and lay the CAPXLV2 face down on a table with the door hanging off the edge of the table, as shown in LiftMaster's illustration.
  3. Identify which knockouts need to be removed based on your application.
  4. Use a center punch tool to remove the knockouts from the outside of the box inward using an appropriately sized punch and hammer. Be careful when removing the knockouts to avoid damaging the CAPXLV2 components.

LiftMaster's illustration marks each knockout with a letter: E = electrical wiring, P = pedestal mount, R = recess mount, S = radio antenna, and W = Wi-Fi antenna.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 11.

Back to contents

Mount the CAPXLV2 (Step 2)

Step 2, mount the CAPXLV2

  1. Attach the goose-neck gasket (provided) if mounting to a goose-neck.
  2. Mount the CAPXLV2 securely to a flat surface or pedestal with appropriate hardware, taking care to route wiring through the appropriate knockouts. Stainless steel hardware is recommended. Use of zinc plated or galvanized hardware is at risk for galvanic corrosion.
  • Ensure the cover can fully open to allow access after the installation is complete.
  • Ensure that the back opening is properly sealed after the installation to avoid water or critters entering the intercom.
  • ADA compliance: when mounting the CAPXLV2 at a pedestrian entrance, to meet ADA compliance, mount the top of the CAPXLV2 screen no higher than 54 inches from the ground.
  • Do not exceed a maximum bolt length of 1.5 in. for the pedestal mount security bolt.
  • For surface and recess mounting, use an appropriate bolt length that secures the CAPXLV2 to the surface completely. The length will vary with the surface of the wall.
  • Make sure any internal wiring is inside the chassis before you close the front panel, to prevent any moisture from entering the chassis.

Swipe sideways to see all columns.

CAPXLV2 recommended mounting screws (page 12)
Mounting configuration Quantity Type / length / diameter
Pedestal mount 4 Metal / 28.62 mm / 6.11 mm
Recess/surface mount 4 Metal / length* / 4.12 mm

*For recess/surface mount applications, the recommended screw lengths are 13.54 mm, 16.56 mm, 19.72 mm, and 22.76 mm. LiftMaster's illustrations show a pedestal mount, a recess mount, and a surface mount.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 12.

Back to contents

Install Antennas (Step 3)

The Security+ 2.0 radio antenna and Wi-Fi antennas must be a minimum of 8 inches (20 cm) apart. Install the antennas on opposite sides of the CAPXLV2. Optional antenna cable kits are available for remote antenna mounting (see Accessories).

Security+ 2.0 radio antenna (if applicable; included in the package)

Used with LiftMaster Passport Security+ 2.0 and wireless communication with LiftMaster UL325 2016 compliant gate operators.

  1. Remove the 3/8 in. knockout on the back of the CAPXLV2.
  2. Secure the radio antenna to the desired knockout on the CAPXLV2.
  3. Connect the radio antenna cable to the main board as shown.

Wi-Fi antenna (if applicable; optional accessory WFBTEXT)

Used for Wi-Fi internet.

  1. Remove the 1/4 in. knockout on the back of the module.
  2. Secure the Wi-Fi antenna to the desired knockout on the CAPXLV2 with the provided gasket, washer, and nut.
  3. Connect the Wi-Fi antenna cable to the main board as shown.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 13.

Back to contents

Ground the Unit (Step 4)

Important (LiftMaster): the CAPXLV2 must always be connected to earth ground, whether by an earth ground rod or other means. An earth ground rod is strongly recommended and should be no further than 12 feet (3.7 m) from the CAPXLV2, using a minimum of 12 gauge wire in most cases. The type and length of earth ground rods vary by region. Contact the AHJ (Authority Having Jurisdiction) in the municipality where you plan to install the CAPXLV2 for correct grounding materials and installation procedures. A proper ground is critical to minimizing the risk of damage to the CAPXLV2 from electrical transients.

Step 4, ground the unit

  1. Connect the ground wire (12 AWG or larger) to the CAPXLV2 main earth ground connection.
  2. Run the wire from the CAPXLV2 to a suitable earth ground.

Note: shield connections on boards should not be connected to the main earth ground connection. Keep the ground wire as straight as possible, and check national and local codes for the proper depth.

  • To AVOID damaging gas, power, or other underground utility lines, contact underground utility locating companies BEFORE digging.
  • Use a PoE injector or router/switch with PoE PSE capability that complies with 802.3bt (Type 3 four wire class 5 compatible) and UL294, with output power of 42-55Vdc and 60 W (max) per port.

LiftMaster's illustration shows 12 AWG minimum ground wire to an earth ground rod, with other ground sources within 12 feet of the access control panel (the existing electrical system ground, or a metallic cold water pipe) and a maximum of 12 feet (3.7 m).

Source: LiftMaster manual, 114-5891-000 Rev. E, page 14.

Back to contents

Connect Power (Step 5)

  • DO NOT use ANY power supply other than those supplied with your CAPXLV2.
  • Use the PoE injector or router/switch with PoE PSE capability that complies with 802.3bt (Type 3 four wire class 5 compatible) and UL294, with output power of 42 - 55 Vdc and 60W (max) per port.
  • DO NOT power electronic strikes and latches with the same power supply used to power the access control panel; doing so will cause DAMAGE to the CAPXLV2. Use ONLY a UL listed burglar alarm or access control system to power electronic strikes and latches.
  • DO NOT connect the power supply or PoE injector to a switched outlet or otherwise controlled AC outlet.
  • DO NOT connect the power supply to the 120 Vac outlet until ALL wiring is completed.
  • DO NOT connect the PoE enabled RJ45 Ethernet cable until ALL wiring is connected, if PoE is used.
  • Install the transient noise suppression device (MOV) supplied with the CAPXLV2 for AC powered devices, and a diode for DC powered devices.
  • DO NOT connect the 24V power supply and PoE power supply to the device at the same time.
  • If the power supply has a ground wire, it must be wired to the GND terminal block to ensure effective grounding.

Using a DC power supply

The outlet for the CAPXLV2 MUST be an external dedicated 120 Vac outlet, wired back to its own 10 Amp minimum circuit breaker. Maximum wire run distances for the power wiring:

Swipe sideways to see all columns.

CAPXLV2 power wire run (page 15)
Wire specification Maximum run distance
14 AWG Up to 300 feet (91.4 m)
16 AWG Up to 200 feet (60.9 m)
18 AWG Up to 100 feet (30.4 m)
  1. Connect 14-18 AWG wire to the stripped secondary DC output wires on the power supply. Black is negative and red is positive.
  2. Remove the PWR INPUT terminal block from the main board.
  3. Connect the power supply wires to the PWR INPUT terminal block (red to +24V and black to GND). Reattach the terminal block to the main board.
  4. Plug the power supply into a 120 Vac outlet after all connections have been made.
  5. Close the CAPXLV2 door.

Note: the green LED on the door of control board will blink and the green LED on the main board will light solid when powered up. The CAPXLV2 will display the LiftMaster logo while booting up. When boot up is complete, the user interface will appear.

Using PoE (Power over Ethernet)

  1. Connect an Ethernet cable to the LAN/PoE connection on the main board (from a PoE injector or a PoE-capable router/switch).
  • When the power supply (low voltage) wiring leaves the enclosure, the wire must be rated for wet and damp locations.
  • High voltage wiring must be run in a separate conduit from low voltage wiring.
  • If the power supply is installed outdoors, it must have its own approved NEMA 4 rated weatherproof electrical enclosure. Use conduit from the power supply enclosure to the controller enclosure. Only the power supply and its input/output wire may be within that enclosure.

Documentation note. The English text gives the PoE output range as 42-55 Vdc on pages 8, 14, and 15, while the French version prints 42-57 Vdc in its specifications and Connect Power page (and 42-55 Vdc on its grounding page). Confirm the PoE range with LiftMaster for your injector or switch.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 15.

Back to contents

Connect Internet (Network Step 1)

The CAPXLV2 can connect to the internet with a wired Ethernet connection or with Wi-Fi (wireless). Make sure you are in Admin Mode before you connect. If you are not in Admin Mode, press the 3 dots in the upper right corner of the CAPXLV2 display, enter the Admin Code, enter the password (LiftMaster prints the default as 888888), press the Network tab on the display, press "NetworkSettings," and then the "Change Network Settings" button. Follow the instructions for your application.

Option 1, wired connection

The Local Area Network (LAN) port is a 10/100 Ethernet interface with an RJ45 jack for connecting the CAPXLV2 to a hub, switch, or router so it can gain internet connectivity. Use a straight (non-crossover) Cat5e or Cat6 cable, referred to as an Ethernet cable in the manual.

  1. Plug the input Ethernet cable into the main board.
  2. Connect an Ethernet cable from the hub, switch, or router to the LAN port on the main board. When connected properly, the green and amber LEDs on the Ethernet port of the main board will light or flicker (the main board is located on the back of the CAPXLV2 display). If the green LED is not lit, check the connections on the CAPXLV2 and the Ethernet hub.
  3. On the display, select Wired Network if dynamic configuration (DHCP) is desired, or select Manual Setup for a static IP address.

Option 2, connect through Wi-Fi (wireless)

  1. On the display, select Wi-Fi Network.
  2. Select the network the CAPXLV2 will use.
  3. Enter the password for the network.
  4. Select Login.

Additional compatibility considerations (LiftMaster): when checking signal strength in CAPXLV2 admin mode, at least two bars are recommended. Use accessory WFBTEXT (Wi-Fi external antenna kit) and WFAEXT (15 ft Wi-Fi extension kit) to move the CAPXLV2 antenna higher up or to a location resulting in two or more bars. If using a Wi-Fi signal strength tool or app, a continuous signal strength of at least -65 dBm (numbers closer to zero are stronger) at the CAPXLV2 must be guaranteed to ensure an acceptable connection to the local network. Hidden network SSIDs are not supported; the network must be selectable from the CAPXLV2 display. Wi-Fi networks requiring secondary authentication (such as hotel and airport Wi-Fi) are not supported.

Validate Setup (Network Step 2)

On the display, select each tab in Admin Mode to validate the setup (network, inputs, outputs, and so on). Once you have validated the setup, exit Admin Mode.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 16.

Back to contents

CAPXLV2 Access Control Wiring

LiftMaster's manual shows wiring examples for gate access (wired, page 17), gate access (wireless, page 18), door access (page 19), an OSDP card reader (page 20), a Wiegand card reader (page 21), a Wiegand output (page 22), and a postal lock (page 23), plus a wiring diagram (page 24). All wiring pages say to disconnect power BEFORE making electrical connections. Input and output port functions can be configured through the myQ Community web portal. The diagrams are not reproduced on this page; use the original manual pages for terminal-level connections, and the notes below, which LiftMaster prints on the diagrams.

  • Disconnect power BEFORE making electrical connections.
  • DO NOT run high voltage power within the enclosure.
  • When wiring a LiftMaster Smart Reader, follow the wiring diagram colors in the Smart Reader install guide; do not use the color guide in the CAPXLV2 manual. For the LiftMaster RFID reader, follow the wiring diagram in the manual for the LMSC1000.

Gate Access, Wired (Page 17)

Gate access can be wired to Relay 1, 2, 3, or 4 on the door of control board. LiftMaster Security+ 2.0 gate operators can also be programmed to communicate wirelessly instead of using a wired connection (see Gate Access, Wireless). The labels on LiftMaster's example include: push button, gate operator, maglock, reader or keypad (12Vdc red, ground black, DATA 0 green, DATA 1 white, green LED orange, red LED brown), external free exit loop detector, request to exit, status (supervised, with an end-of-line resistor), primary relay, auxiliary relay (alarm bypass, light), and an RFID antenna with Wiegand output.

  • Gate operator connection: connect to the gate operator's auxiliary closed limit switch; refer to the gate operator manual. The status (supervised) connection is not applicable for wireless gate operator connections.
  • Maglock: use 18-22 AWG wire and a separate power supply (not provided). DO NOT use the controller's power supply. For DC power, install a 1N4005 diode or equivalent. For AC power, install a Siemens S10K30MOV (metal oxide varistor) (provided) or equivalent.
  • End-of-line resistor: 1k ohm.
  • RFID antenna: power it separately (power not provided); DO NOT use the controller's power supply.
  • Wiring: keep the length of unshielded wires to a minimum to avoid electrical noise. For a KPR2000 keypad, wire the pink and black (ground) wires together.
  • Light or load on the auxiliary relay: the diagram's labels include an isolation relay, a low voltage power supply, and the load, line, and neutral connections.
  • UL evaluation: the maglock and alarm bypass were not evaluated by UL.

Documentation note. The "do not run high voltage power" note on the gate access and door access diagrams (pages 17 and 19) names the "CAP4APL" enclosure, not the CAPXLV2. It appears to be carried over from another LiftMaster product; the instruction applies to the CAPXLV2 enclosure.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 17.

Back to contents

Gate Access, Wireless (Page 18)

The CAPXLV2 can communicate wirelessly with LiftMaster UL325 gate operators to send open commands, monitor gate position, and send email notifications if an error occurs in the operator (email notifications are configured in myQ). Up to 8 gate operators can be paired with the CAPXLV2, one for each relay. If using dual gates, program the CAPXLV2 to the primary operator. Use of this feature requires the optional Passport antenna kit.

Pair a gate operator wirelessly

  1. Enter Admin Mode. Press the 3 dots in the upper right corner of the CAPXLV2 display and enter the Admin Code.
  2. Select Outputs and Relay. Select the Outputs tab, then select the desired relay on the left-hand side (1 through 8).
  3. Press the LEARN button on the gate operator. Press and release the LEARN button on the primary operator. The green XMITTER LED will light. The operator will time out of programming mode after 180 seconds.
  4. Press the LEARN button on the gate operator again. Press and release the LEARN button again on the primary operator. The yellow NETWORK LED will light.
  5. Select LEARN on the display. Select the LEARN button on the display and the button will go from blue to red. The gate operator will beep once, the CAPXLV2 learn button will change to "Unlearn," and the NETWORK LED on the gate operator will turn off, indicating programming is successful. Four beeps or blinks indicate you are not programming to the primary operator; reattempt programming from the other operator.
  6. Validate. Validate functionality by selecting Test Relay on the CAPXLV2 display.

See also the compatibility limits in Specifications (750 feet open air, Security+ 2.0 and listed operator firmware, not compatible with barrier gate operators).

Source: LiftMaster manual, 114-5891-000 Rev. E, page 18.

Back to contents

Door Access (Page 19)

Door access can be wired to Relay 1, 2, 3, or 4 on the door of control board. The labels on LiftMaster's door access example include: push button, door strike, maglock, proximity sensor, request to exit (REX), supervised (door status) with a supervised or non-supervised door sensor, reader or keypad (12Vdc red, ground black, DATA 0 green, DATA 1 white, green LED orange, red LED brown), an RFID antenna with Wiegand output, primary relay, auxiliary relay (alarm bypass and a light), and the isolation relay, low voltage power supply, load, line, and neutral. The diagram itself is the authority for which device connects to which terminal.

  • Maglock and door strike power: use a separate power supply (not provided). DO NOT use the controller's power supply for the maglock. Use 18-22 AWG wire.
  • Surge protection: for DC power, install a 1N4005 diode or equivalent. For AC power, install a Siemens S10K30MOV (metal oxide varistor) (provided) or equivalent.
  • Supervised input: the diagram shows an end-of-line (EOL) resistor (1k ohm) for the supervised door sensor.
  • Wiring: keep the length of unshielded wires to a minimum to avoid electrical noise. For a KPR2000 keypad, wire the pink and black (ground) wires together.
  • UL evaluation: the maglock, door strike, and alarm bypass were not evaluated by UL.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 19.

Back to contents

OSDP Card Reader (Page 20)

The CAPXLV2 is designed to connect a single or multiple OSDP readers. LiftMaster says to install an OSDP reader as follows.

Install an OSDP reader

  1. Disconnect power from the CAPXLV2.
  2. Prepare the RS-485 cables before the connection by adding the matching resistors (100 ohms) to both ends of the cable.
  3. Connect one end of the RS-485 cables and 12VDC power to the OSDP connector on the CAPXLV2 main board.
  4. Turn on power to the CAPXLV2 and make sure it is in Admin Mode.
  5. Go to the OSDP tab in Admin Mode.
  6. Toggle Enable Install New Reader.
  7. Make sure the new OSDP reader has default address 0 by following the manufacturer's recommendation. If not, connect the OSDP reader to the 12V power line and GND and, within 60 seconds of the reader power cycle, tap the reader with the configuration card (5044-FEA-OSDP-018) to set it to the manufacturer default, then disconnect the 12V power line.
  8. Connect the new OSDP reader to the RS-485 cables.
  9. The CAPXLV2 should discover the connected reader and create the reader in myQB. The reader should turn its LED to amber. The OSDP reader is now installed.
  10. To install more OSDP readers, follow steps 7 through 9 for each new OSDP reader.

Uninstall or delete an OSDP reader

  1. Make sure the OSDP reader to be deleted is connected to RS-485.
  2. Go to the OSDP tab in Admin Mode.
  3. Select the OSDP reader to be deleted from the Connected Readers.
  4. Click the Delete button.
  5. Click Delete in the confirmation dialog box.
  6. Check that the deleted reader is not displayed under Connected Readers.
  7. Disconnect the deleted reader from the RS-485 cable and the 12V power line.

Notes (LiftMaster): the CAPXLV2 can only install one OSDP reader at a time. You must complete steps 7 through 9 for an OSDP reader before you connect another new OSDP reader to the 12 V power. Never disconnect an OSDP reader before uninstalling or deleting it from the Admin UI.

LiftMaster's illustration shows the daisy-chain connection from the OSDP connector (GND, Dp, Dn, +12VDC) with 100 ohm external resistors at each end of the chain.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 20.

Back to contents

Wiegand Card Reader (Page 21)

The CAPXLV2 is designed to fit multiple readers on the flexible reader mount inside the chassis.

  1. Disconnect power from the CAPXLV2.
  2. Secure the reader to the mounting plate with the supplied screws.
  3. Place the reader against the glass in the CAPXLV2.
  4. Secure the reader and mounting plate assembly into the CAPXLV2 with two screws in the side wings.
  5. Apply silicone around the cable hole.
  6. The reader can be wired to any of the 4 Wiegand inputs on the door of control board(s). Insulate any unused wires from the CAPXLV2 to prevent a short. (Refer to the instructions provided with your reader for more information.)
  7. Reconnect power to the CAPXLV2.
  8. Refer to myQ for programming.

Note: to fit the mounting plate and the cavity, the reader dimensions cannot exceed 4 in. x 2 in.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 21.

Back to contents

Wiegand Output (Page 22)

Disconnect power BEFORE making electrical connections. The CAPXLV2 offers a Wiegand output capable of 26-bit transmission of the following data, and/or:

  • Success call with access granted by the resident: the CAPXLV2 will provide a myQ Community specified facility code followed by the Directory Code of the resident that granted access.
  • Successful access through entry code: the CAPXLV2 will provide a myQ Community specified facility code followed by the successful entry code.
  • Successful access with a credential: the CAPXLV2 will pass along the successful credential facility code and ID.

LiftMaster's illustration connects door of control board 1's Wiegand output to a third party access system Wiegand input. This device/reader must be listed to UL 294.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 22.

Back to contents

Postal Lock (Page 23)

  1. Remove the wing nut and plug. Discard the wing nut and plug.
  2. Remove 4 mounting nuts from the studs.
  3. Install the postal lock using the 4 nuts from step 2.
  4. Cut the factory installed wire tie from the postal lock switch.
  5. Configure the postal lock to an access point in the configuration settings for this device on the myQ Community web portal. The postal lock may be connected to Monitored Input 2 by default.
  6. Test the postal lock to ensure proper mapping of the access point to the postal lock.

The postal lock switch is wired from the factory.

Note: the postal lock cable length shall not exceed 98.5 ft (30 m). Configuration through the myQ Community web portal is required.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 23.

Back to contents

CAPXLV2 Wiring Diagram (Page 24)

LiftMaster's wiring diagram (page 24) shows the internal connections between these labeled parts: the touchscreen, display and display data, main board (with 24VDC power in, DIAG, MIC, battery behind board, Ethernet/PoE, antenna ports, radio, status LEDs, learn, speaker, OSDP, USB camera, USB 1 and 2, RF cable bracket, DOC 1 and DOC 2, and postal lock), door of control boards 1 and 2 (DOC 1 and DOC 2, each with relays, inputs, and Wiegand ports), the microphone, camera, speaker, Wi-Fi antenna, 24V power supply, and postal lock switch. Its notes say: LiftMaster is not responsible for conflicts between the information listed in the wiring diagram and the requirements of your local building codes (the information is for suggested use ONLY; check your local codes BEFORE installation), and DO NOT connect the 24V power supply and PoE power supply to the device at the same time. Use the original page 24 for the diagram itself.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 24.

Back to contents

CAPXLV2 Repair Parts and Accessories

LiftMaster's page 25 lists two tables and the headings "Accessories" and "Repair Parts." The links below open related All Security Equipment category pages and do not by themselves confirm that we stock an item or that it fits your CAPXLV2.

Repair Parts

Swipe sideways to see all columns.

CAPXLV2 repair parts as printed by LiftMaster (page 25)
Item Part number
Door of control board and covers K41-0422-000
Main board kit K41-0366-000
Reader mounting plate kit K41-0367-000
Rear housing assembly kit K41-0368-000
Wiring kit K41-0369-000
Speaker kit K41-0370-000
Front panel and display kit K41-0371-000
Postal lock switch K41-0219-000
Cam lock and kit K41-0430-000

Compatible CAPXLV2 Accessories

Swipe sideways to see all columns.

CAPXLV2 accessories as printed by LiftMaster (page 25)
Item Part number
Flush mount trim kit CAPXLV2TK
Hood for pedestal and surface mount applications CAPXLV2HOOD
Trim plate and hood together CAPXLV2TKHD
Power supply K41-0227-000
USB camera kit K41-0398-000
Radio antenna extension (15 foot) G86LM
Wi-Fi antenna extension (15 foot) WFAEXT
Wi-Fi/Bluetooth extension antenna WFBTEXT
ESARM antenna XMANTKIT
UHF long range RFID reader LMSC1000
Wiegand keypad/proximity reader KPR2000*
LiftMaster Smart Reader and keypad with OSDP support SRDRST or SRDRKP
Connected Access Portal, 2 door CAP2D
Passport 3-button visor control MAX PPV3M
Passport 3-button mini remote control MAX PPK3M
Passport 3-button mini proximity remote control MAX PPK3PHM
Passport Lite 1-button visor remote PPLV1-X**
Passport Lite 1-button key chain remote PPLK1-X**
Passport Lite 1-button mini proximity remote PPLK1PH-X**

*KPR2000 is verified for supplementary use only. **Available in 10 and 100 packs; replace X with 10 or 100. LiftMaster also notes that if you have a specific model of reader or keypad that is not listed on the LiftMaster website, you should contact LiftMaster Technical Support to determine compatibility.

Shop related products: intercom and telephone entry systems | keypads | fob and card readers | remotes and receivers | power supplies | gate operators

Documentation notes. (1) In the English text of page 25, the heading "Accessories" appears first and "Repair Parts" after both tables, while the table of contents lists Repair Parts before Accessories. This page assigns the kits for the CAPXLV2's own components to Repair Parts and the trim kits, antennas, readers, keypad, and remotes to Accessories based on their content. (2) The English table lists the cam lock and kit as K41-0430-000, while the French table prints K41-0215-000 for the same item. Confirm the part number with LiftMaster before ordering.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 25.

Back to contents

CAPXLV2 Configuration Sheet

LiftMaster provides a configuration sheet (page 26) to record device information and configuration settings. It has fields for the CAPXLV2 name and notes, and, for each of Access Point 1 and Access Point 2: the door/gate name; the inputs (type, input name, EOL yes or no, and hardware mapping for the first to fourth monitored inputs); the relays (type, relay name, and N.O./N.C.); and the readers (type, reader name, and hardware mapping). LiftMaster notes that any user of the system is subject to the terms outlined in the product EULA. Print the sheet from the original manual to fill it in.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 26.

Back to contents

The manual's legal page (page 27) includes the following topics. It is summarized here; read the original page for the full text.

  • FCC compliancy: the equipment was tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. LiftMaster lists corrective measures if the equipment causes harmful interference: increase the distance between the equipment and the receiver, connect the equipment to a different circuit, and consult the dealer for help.
  • Canada, Underwriters Laboratories: the CAPXLV2 shall be installed in accordance with Part 1 of the Canadian Electrical Code.
  • Documentation disclaimer: information in the manual is subject to change without notice and does not represent a commitment on the part of LiftMaster; LiftMaster directs readers to LiftMaster.com for the most up-to-date information. The document and its data shall not be duplicated, used, or disclosed to others for procurement or manufacturing except with LiftMaster's written permission.
  • UL 294 ratings printed: access control unit Endurance: Level 2; mobile credential Endurance Level 2 using mobile phone Bluetooth, 25,000 cycles; Line security: Level 1; Destructive Attack: Level 1; Power Standby: Level 1.
  • FCC and Innovation, Science and Economic Development Canada: the device complies with part 15 of the FCC rules and Canadian licence-exempt RSS standards. Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. The device must be installed to maintain a minimum 20 cm (8 in.) distance between users or bystanders and the device. The equipment complies with FCC RF and ISED radiation exposure limits for an uncontrolled environment, and its antenna(s) must not be co-located or operating with any other antenna or transmitter.
  • Local requirements: refer to the local jurisdiction for any specific requirements, such as physical signage that may be required.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 27.

Back to contents

CAPXLV2 Warranty

Per LiftMaster's warranty (page 28): "2 year warranty." For more warranty information, LiftMaster directs you to liftmaster.com/warranty or to call (800) 528-2806. The manual's last page prints the document number 114-5891-000 (Rev. E), ©2025 Chamberlain Group, LLC, and the address Chamberlain Group, LLC, 300 Windsor Drive, Oak Brook, IL, 60523, United States.

All Security Equipment note. If you bought your CAPXLV2 from All Security Equipment, see our refund policy and our Help Center for how manufacturer warranty returns are handled.

Source: LiftMaster manual, 114-5891-000 Rev. E, page 28.

Back to contents

Frequently Asked Questions About the LiftMaster CAPXLV2

How many doors or gates can one CAPXLV2 control?

Per the manual, each door of control board controls up to 4 access points, and the CAPXLV2 can control up to 8 access points in total (page 6). It can also pair wirelessly with up to 8 gate operators, one for each relay (page 18). See Door of Control Board Overview.

How is the CAPXLV2 powered?

By the supplied 24V DC power supply (72W, 3A max) or by PoE (42-55VDC, 802.3bt Type 3 Class 5 or 6, Mode B). Do not connect the 24V supply and PoE at the same time (pages 8, 15, and 24). See Connect Power.

What does the CAPXLV2 need to work?

Per the manual: a myQ Community account with a service subscription (page 10), a power source (24V supply on a dedicated 120 Vac outlet, or PoE) (page 15), an internet connection by Ethernet or Wi-Fi (page 16), and VoIP service through Phone.com for the calling function (page 10).

How do I enter Admin Mode?

Press the 3 dots in the upper right corner of the display and enter the Admin Code; for network settings the manual also asks for a password and prints the default as 888888 (pages 16 and 18). See Connect Internet.

What Wi-Fi does the CAPXLV2 support?

802.11 a/b/g/n and 802.11ac at 2.4 GHz and 5 GHz with WPA3-SAE, WPA2-PSK/WPA3-SAE, WPA2-PSK, or WPA/WPA2-PSK, up to 500 feet with the external antenna. It does not support hidden SSIDs or networks that require secondary authentication such as hotel or airport Wi-Fi (pages 8 and 16).

Which gate operators can the CAPXLV2 talk to wirelessly?

LiftMaster Security+ 2.0 gate operators, 2018 LiftMaster gate operators (firmware v4.4 and later), and HD operators (firmware v3.3 or later), up to 750 feet open air. It is not compatible with LiftMaster barrier gate operators, and wireless linking needs the optional Passport antenna kit (pages 8 and 18). See Gate Access, Wireless.

How many OSDP readers can I connect?

LiftMaster's main board overview and specifications say up to 4 readers in a daisy chain within 1000 ft, with 8 planned for a future firmware release, but its wire specification chart says up to 8 units. See OSDP Card Reader and the note in Specifications.

Does the CAPXLV2 support mobile credentials?

Yes, using Bluetooth with myQ Community app version 3.4.0 or above on a smartphone running iOS 15, 16, or 17, or Android 7 (Nougat) to Android 13, secured by a PIN or biometric (page 8).

What ground does the CAPXLV2 need?

The CAPXLV2 must always be connected to earth ground. LiftMaster strongly recommends an earth ground rod no more than 12 feet (3.7 m) away, with at least 12 AWG wire (page 14). See Ground the Unit.

How high should I mount the CAPXLV2?

At a pedestrian entrance, to meet ADA compliance, mount the top of the screen no higher than 54 inches from the ground (page 12). See Mount the CAPXLV2.

Can I power a maglock or door strike from the CAPXLV2 power supply?

No. LiftMaster says not to use the controller's power supply for the maglock, and to use only a UL listed burglar alarm or access control system to power electronic strikes and latches (pages 15, 17, and 19).

What warranty does the CAPXLV2 have?

LiftMaster prints a 2 year warranty and directs you to liftmaster.com/warranty or (800) 528-2806 for more information (page 28). See CAPXLV2 Warranty.

Does the manual come in other languages?

Yes. LiftMaster's combined PDF has the English manual first (pages 1 to 28), followed by French and Spanish versions. This page presents the English version.

Original LiftMaster CAPXLV2 Documentation

This HTML resource is presented by All Security Equipment, is not a LiftMaster publication, and does not replace the original manufacturer documentation. It is based on LiftMaster's CAPXLV2 Smart Video Intercom L installation manual, document 114-5891-000 (Rev. E), ©2025 Chamberlain Group, LLC.

Check LiftMaster's product page for the current revision before relying on any document, because LiftMaster may update them.

Need the intercom itself? All Security Equipment sells the LiftMaster CAPXLV2 Smart Video Intercom L for gated communities, multi-tenant buildings, and other properties with several access points.

This resource was last updated November 11, 2026. Based on LiftMaster document 114-5891-000 Rev. E.