This page presents the LiftMaster LA412UL residential 12 Vdc solar-powered vehicular swing gate operator installation manual as searchable, linkable HTML, for the LA412PKGUL single arm package, the LA412DC primary 12 Vdc actuator arm, and the LA412DCS secondary 12 Vdc actuator arm: specifications, safety requirements, installation, wiring, adjustment, programming, troubleshooting, diagnostic codes, maintenance, solar panels, and replacement parts.

Source and scope. This HTML technical resource is based on official LiftMaster documentation for the LA412UL (document 01-39383, revision B). It is not published by LiftMaster, and All Security Equipment is not the manufacturer. Always verify that the instructions apply to your operator's model and manufacturing date, and follow the original LiftMaster documents when they differ from this page.

Text under "Source: LiftMaster manual" lines follows the manufacturer's documentation. Blue boxes labeled "All Security Equipment note" are our own supplemental guidance and are not manufacturer instructions.

LiftMaster LA412 solar-powered vehicular swing gate operator with 12V 10W solar panel
LiftMaster LA412 solar-powered vehicular swing gate operator. Product image from All Security Equipment.

Documentation Information

Manufacturer
LiftMaster (The Chamberlain Group, Inc.)
Models
LA412PKGUL (single arm package), LA412DC (primary 12 Vdc actuator arm), and LA412DCS (secondary 12 Vdc actuator arm for dual swing gate applications). One manual covers all three.
Equipment type
Residential 12 Vdc, solar-powered vehicular swing gate operator (Class I)
Document type
Installation Manual (English)
Manufacturer document number
01-39383
Manual revision
B (printed as 01-39383B)
Manual copyright / publication
© 2018 The Chamberlain Group, Inc. The manual does not print a separate revision date.
Source
Official LiftMaster documentation for the LA412UL (see Original LiftMaster Documentation)
HTML resource last updated
October 12, 2026

Common tasks: Set the limits | Program a remote | Wiring diagram | Diagnostic codes | Gate will not close | Replace batteries | Replacement parts

LiftMaster LA412UL Manual Overview

The LiftMaster LA412UL is a residential 12 Vdc vehicular swing gate operator that runs from solar power only (the manual lists the main AC supply as "N/A - Solar Only"). LiftMaster's installation manual (document 01-39383 revision B) covers the LA412PKGUL single arm package, the LA412DC primary 12 Vdc actuator arm for single swing gate applications, and the LA412DCS secondary 12 Vdc actuator arm for dual swing gate applications. LiftMaster states that the operator requires a LiftMaster external monitored entrapment protection device to be installed in all entrapment zones, and that it must be installed and serviced by a trained gate systems technician only.

What Is in the LA412UL Carton

Not shown in LiftMaster's carton illustration (page 6): documentation packet and hardware bag. LiftMaster's hardware inventory lists the following, with quantities shown for the LA412DC (doubled for the LA412DCS):

  • Flat washer 5/16 in. (1), lock washer 5/16 in. (1), hex nut 5/16 in.-18 (1), hex bolt 5/16 in.-18 x 1-1/2 in. (1)
  • Flat washer 3/8 in. (3), lock washer 3/8 in. (3), hex nut 3/8 in.-16 (3), hex bolt 3/8 in.-16 x 1-1/2 in. (1), carriage bolt 3/8 in. x 5-15/16 in. (2)
  • Key (2), keylock cap, pin (2), hairpin clip (2)

Optional accessories (LiftMaster, page 6): the large metal control box for solar applications (Model XLSOLARCONTUL), ideal for installations that require additional room in the control box (batteries not included), which requires two 33AH batteries, a battery tray, and a solar battery harness; and a push-to-open bracket (Model 50-19503) if your application requires the gate to be pushed open. See Accessories.

LiftMaster LA412 carton inventory: standard control box, brackets, solar panel, gate operator, warning signs, and LA412DCS dual-gate accessories

Source: LiftMaster manual, 01-39383 revision B, page 6.

Back to contents

LiftMaster LA412UL Specifications

LA412UL operator specifications as printed by LiftMaster (page 7)

Swipe sideways to see all columns.

LA412UL operator specifications as printed by LiftMaster (page 7)
Specification LA412UL
Usage classification Class I
Main AC supply N/A - Solar Only
System operating voltage 12 Vdc battery run / solar charge
Accessory power 12 Vdc, 500 mA max. for ON + SW (switched)
Solar power max 12 Vdc at 30 watts max.
Maximum gate weight / length 850 lbs. (385.6 kg) / 10 ft (3.0 m); 750 lbs. (340.2 kg) / 12 ft (3.7 m); 650 lbs. (294.8 kg) / 14 ft (4.3 m); 550 lbs. (249.5 kg) / 16 ft (4.9 m)
90 degree travel time* < 23 seconds
Maximum travel range* 115 degrees
Maximum daily cycle rate 50 cycles / day
Maximum duty cycle 4 min on
Operating temperature -20°C to 60°C (-4°F to 140°F)
Expansion board Optional
External entrapment protection device inputs (non-contact and/or contact) Main board: up to 2 close entrapment protection devices and 1 open entrapment protection device. Expansion board: up to 3 entrapment protection devices configurable to either close or open direction and up to 4 edge sensors using wireless edge sensor kit model LMWEKITU.

*Travel time and range are affected by the A and B mounting dimensions (see Determine Mounting Location).

Source: LiftMaster manual, 01-39383 revision B, page 7.

Back to contents

Important Safety Information

This section reproduces the safety requirements that LiftMaster places at the front of the LA412UL manual (pages 1 to 5). Safety text is kept close to the manufacturer's wording on purpose.

Who Should Install and Service the LA412UL

  • THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED GATE SYSTEMS TECHNICIAN ONLY.
  • The operator requires a LiftMaster external monitored entrapment protection device to be installed in all entrapment zones.

LiftMaster's manual also includes a Safety Symbol and Signal Word Review on page 2. See the original manual for the symbols and signal words LiftMaster uses.

Source: LiftMaster manual, 01-39383 revision B, page 1.

Gate Operator Usage Classes

LiftMaster's manual defines four vehicular gate operator usage classes (page 3). The LA412UL specifications list Class I.

  • Class I, Residential Vehicular Gate Operator: a vehicular gate operator (or system) intended for use in garages or parking areas associated with a residence of one to four single families.
  • Class II, Commercial/General Access Vehicular Gate: a vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotel, garages, retail store, or other buildings accessible by or servicing the general public.
  • Class III, Industrial/Limited Access Vehicular Gate: a vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not accessible by or intended to service the general public.
  • Class IV, Restricted Access Vehicular Gate Operator: a vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.

Source: LiftMaster manual, 01-39383 revision B, page 3.

UL 325 Entrapment Protection Requirements for the LA412UL

  • A minimum of two independent* monitored entrapment protection devices are required to be installed at each entrapment zone.
  • Every installation is unique. It is the responsibility of the installer to install external monitored entrapment protection devices in each entrapment zone.
  • This vehicular swing gate operator will operate only after installation of a minimum of two independent* monitored entrapment protection devices in either the open or close direction. If no entrapment zone exists in the other direction of gate travel, then the inherent device (built into the operator) is all that is required in that direction.
  • Entrapment protection device types include inherent (built into the operator), monitored external photoelectric sensors, or monitored external edge sensors.
  • This operator is provided with an inherent entrapment protection device built into the operator that serves as one of the two independent devices.

* Independent: the same type of device shall NOT be used for both entrapment protection devices.

IMPORTANT SAFETY INSTRUCTIONS. To reduce the risk of INJURY or DEATH:

  • READ AND FOLLOW ALL INSTRUCTIONS.
  • NEVER let children operate or play with gate controls. Keep the remote control away from children.
  • ALWAYS keep people and objects away from the gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
  • Test the gate operator monthly. The gate MUST reverse on contact with an object or reverse when an object activates the noncontact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of INJURY or DEATH.
  • Use the emergency release ONLY when the gate is not moving.
  • KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.
  • The entrance is for vehicles ONLY. Pedestrians MUST use separate entrance.
  • SAVE THESE INSTRUCTIONS.

All Security Equipment note. The manual's safety instructions on page 3 say "emergency release," while the maintenance instructions on page 36 and the operation section on page 32 say "manual disconnect release" and "manual release." They describe the same release lever.

Source: LiftMaster manual, 01-39383 revision B, page 3.

Safety Installation Information

  1. Vehicular gate systems provide convenience and security. Gate systems are comprised of many component parts. The gate operator is only one component. Each gate system is specifically designed for an individual application.
  2. Gate operating system designers, installers and users must take into account the possible hazards associated with each individual application. Improperly designed, installed or maintained systems can create risks for the user as well as the bystander. Gate systems design and installation must reduce public exposure to potential hazards.
  3. A gate operator can create high levels of force in its function as a component part of a gate system. Therefore, safety features must be incorporated into every design. Specific safety features include edge sensors (contact), photoelectric sensors, vertical posts, and instructional and precautionary signage.
  4. Install the gate operator only when: (a) the operator is appropriate for the construction and the usage class of the gate; (b) all exposed pinch points are eliminated or guarded, and guarding is supplied for exposed rollers.
  5. The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
  6. The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment. Swinging gates shall not open into public access areas.
  7. The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. (Per LiftMaster, one or more contact sensors shall be located on the bottom edge of a swing gate when the bottom edge is greater than 4 inches (10.1 cm) but less than 16 inches (406 mm) above the ground at any point in its arc of travel; see item 12.)
  8. Permanently mounted access controls intended for users to activate must be located at least 6 feet (1.8 m) away from any moving part of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or easily accessible controls shall have a security feature to prevent unauthorized use. Exception: emergency access controls only accessible by authorized personnel (e.g. fire, police) may be placed at any location in the line-of-sight of the gate.
  9. The Stop and/or Reset (if provided separately) must be located in the line-of-sight of the gate. Activation of the reset control shall not cause the operator to start.
  10. A minimum of two (2) WARNING SIGNS shall be installed in the area of the gate. Each placard is to be visible by persons located on the side of the gate on which the placard is installed.
  11. For a gate operator utilizing a non-contact sensor: (a) reference the owner's manual regarding placement of non-contact sensors for each type of application (see Install Entrapment Protection); (b) care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is still moving; (c) one or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a moving gate or barrier.
  12. For a gate operator utilizing a contact sensor such as an edge sensor: (a) one or more contact sensors shall be located where the risk of entrapment or obstruction exists; (b) a hard wired contact sensor shall be located and its wiring arranged so the communication between the sensor and the gate operator is not subject to mechanical damage; (c) a wireless device such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals is not obstructed or impeded by building structures, natural landscaping or similar obstruction, and shall function under the intended end-use conditions; (d) one or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a swing gate is greater than 4 inches (10.1 cm) but less than 16 inches (406 mm) above the ground at any point in its arc of travel, one or more contact sensors shall be located on the bottom edge.

Source: LiftMaster manual, 01-39383 revision B, page 4.

Gate Construction Requirements (ASTM F2200)

LiftMaster states that vehicular gates should be installed in accordance with ASTM F2200, Standard Specification for Automated Vehicular Gate Construction (contact ASTM at 610-832-9585 or www.astm.org for a copy). The manual lists these provisions (page 5):

General requirements

  • 1.1 Gates shall be constructed in accordance with the provisions given for the appropriate gate type listed; refer to ASTM F2200 for additional gate types.
  • 1.2 Gates shall be designed, constructed and installed to not fall over more than 45 degrees from the vertical plane, when a gate is detached from the supporting hardware.
  • 1.3 Gates shall have smooth bottom edges, with vertical bottom edged protrusions not exceeding 0.50 inches (12.7 mm) when other than the exceptions listed in ASTM F2200.
  • 1.4 The minimum height for barbed tape shall not be less than 8 feet (2.44 m) above grade and for barbed wire shall not be less than 6 feet (1.83 m) above grade.
  • 1.5 An existing gate latch shall be disabled when a manually operated gate is retrofitted with a powered gate operator.
  • 1.6 A gate latch shall not be installed on an automatically operated gate.
  • 1.7 Protrusions shall not be permitted on any gate; refer to ASTM F2200 for exceptions.
  • 1.8 Gates shall be designed, constructed and installed such that their movement shall not be initiated by gravity when an automatic operator is disconnected. For a vehicular horizontal swing gate (1.8.1), this shall not result in continuous, unimpeded movement in either direction along the arc of its path of travel.
  • 1.9 For pedestrian access in the vicinity of an automated vehicular gate, a separate pedestrian gate shall be provided. The pedestrian gate shall be installed in a location such that a pedestrian shall not come in contact with a moving vehicular access gate. A pedestrian gate shall not be incorporated into an automated vehicular gate panel.

Specific applications

  • 2.1 Any non-automated gate that is to be automated shall be upgraded to conform to the provisions of this specification.
  • 2.2 This specification shall not apply to gates generally used for pedestrian access and to vehicular gates not to be automated.
  • 2.3 When the gate operator requires replacement, the existing gate shall be upgraded to conform to the provisions of this specification.
  • 2.4 When the gate of an automated gate system requires replacement, the new gate shall conform to the provisions of this specification.

Vehicular horizontal swing gates

  • 3.1 The following provisions apply to Class I, Class II and Class III vehicular horizontal swing gates. 3.1.1 Gates shall be designed, constructed and installed so as not to create an entrapment area between the gate and the supporting structure or other fixed object when the gate moves toward the fully open position, subject to 3.1.1.1 and 3.1.1.2.
  • 3.1.1.1 The width of an object (such as a wall, pillar or column) covered by a swing gate when in the open position shall not exceed 4 inches (102 mm), measured from the center line of the pivot point of the gate. Exception: for a gate not in compliance with this provision, the defined area must be provided with entrapment protection per UL 325.
  • 3.1.1.2 Except for the zone specified in Section 3.1.1.1, the distance between a fixed object such as a wall, pillar or column, and a swing gate when in the open position shall not be less than 16 inches (406 mm). Exception: for a gate not in compliance with this provision, the defined area must be provided with entrapment protection per UL 325.
  • 3.2 Class IV vehicular horizontal swing gates shall be designed, constructed and installed in accordance with security related parameters specific to the application in question.

Source: LiftMaster manual, 01-39383 revision B, page 5.

Back to contents

LiftMaster LA412UL Installation

LiftMaster presents LA412UL installation as twelve steps, followed by limit and force adjustment and an obstruction test. Each step below is labeled with the matching LiftMaster step number.

  1. Step 1, Attach brackets to operator
  2. Step 2, Determine mounting location
  3. Step 3, Position the operator
  4. Step 4, Secure the brackets
  5. Step 5, Install the control box
  6. Step 6, Earth ground rod
  7. Step 7, Wire the operator arm to the control board
  8. Step 8, Dual gate setup
  9. Step 9, Install entrapment protection
  10. Step 10, Install solar panels
  11. Step 11, Power wiring
  12. Step 12, Finish installation

After Step 12, continue with limit and force adjustment and the obstruction test.

Installation Requirements and Tips

  • To AVOID damaging gas, power or other underground utility lines, contact underground utility locating companies BEFORE digging more than 18 inches (46 cm) deep.
  • ALWAYS wear protective gloves and eye protection when changing the battery or working around the battery compartment.

LiftMaster's do's:

  • Weld a horizontal bar across the entire gate on any installation for strength. Make sure that the operator is mounted level or it will not function properly.
  • The operator can be mounted on top of the gate frame.
  • The operator must be installed at least 12 inches (30 cm) from the ground.
  • Make sure there is slack in the operator cable.

LiftMaster's don'ts:

  • DO NOT install upside down.
  • DO NOT install on ANY pedestrian passageways, doorways, or gates.
  • DO NOT install next to sprinklers or any area that may expose the bottom of the operator to water.
  • DO NOT over-bend the operator cable. Doing this will cause the wires to eventually break.
  • DO NOT install on uphill or downhill gates.
  • DO NOT weld the crossbar on just a few pickets, or they could bend.

Source: LiftMaster manual, 01-39383 revision B, page 9.

Site Preparation

  • Check the national and local building codes BEFORE installation.
  • Trench: trench and install conduit. Before trenching, contact underground utility locating companies. Conduit must be UL approved for low and high voltage.
  • Safety: entrapment protection devices are required to protect against any entrapment or safety conditions encountered in your gate application. Install a warning sign (two provided) on the inside and outside of the property, where easily visible.
  • Gate: the gate must be constructed and installed according to ASTM F2200 standards (see Gate Construction Requirements), and must fit the specifications of the operator (see Specifications).
  • Additional accessories: vehicle loops allow the gate to stay open when vehicles are obstructing the gate path. They are suggested for vehicles 14 feet (4.27 m) or longer and are not required but are recommended. Before installing your access control device(s), complete a site survey and determine the best device for your site needs.

Check your gate (LiftMaster): the gate MUST be level. The gate and gate post MUST be plumb. The gate MUST have a smooth bottom edge, and no protrusions should exist. Remove ANY/ALL wheels from the bottom of the gate. The gate MUST NOT hit or drag across the ground. The gate MUST swing freely and be supported entirely by its hinges.

Documentation note. Page 8 of the manual says to refer to page 4 for gate construction, but the gate construction information is on page 5 (page 4 is Safety Installation Information). See Gate Construction Requirements.

Source: LiftMaster manual, 01-39383 revision B, page 8.

Attach Brackets to the Operator (Step 1)

Step 1, attach brackets to the operator

  1. Insert the key into the lock on the release lever and turn it 180° counterclockwise.
  2. Turn the release lever 180° counterclockwise. The operator is now in manual mode.
  3. Assemble the gate post bracket by placing the pull-to-open bracket on top of the post bracket.
  4. Insert the bolt through both brackets and secure with washer, lock washer and nut.
  5. Attach the post bracket assembly to the operator using pins and hairpin clips.
  6. Attach the gate bracket to the operator using pins and hairpin clips.

Source: LiftMaster manual, 01-39383 revision B, page 10.

Determine the Mounting Location (Step 2)

Before proceeding, begin with the gate in the fully closed position. There are two methods for determining the proper location of the post brackets; either method will work depending on preference: the paper template (located on the back page of the manual, which must be cut out) or a tape measure. LiftMaster notes that there should only be a maximum of 4 inches (10.2 cm) from the center of the hinge to the edge of the post or column. If the distance is greater than 4 inches (10.2 cm), entrapment protection for this area is required.

Template method

  1. Close the gate.
  2. Place the template (provided on the back page of this manual) under the center of the gate hinge point.
  3. Use a screwdriver or dowel rod to temporarily mark the location in front of the gate post.

Tape measure method

  1. Close the gate.
  2. Place the measuring tape under the center of the gate hinge point and measure out 7 inches (17.8 cm).
  3. Use a screwdriver or dowel rod to temporarily mark the location of the first measurement.
  4. Measure 7 inches (17.8 cm) from the previous mark.
  5. Use the screwdriver or dowel rod to mark the location of the second measurement.

Alternate dimensions. The ideal installation measurements are A = 7 inches (17.8 cm) and B = 7 inches (17.8 cm). If different measurements are used, the sum of A and B cannot be greater than 15 inches (38.1 cm).

LA412UL mounting dimension chart (A and B)

Swipe sideways to see all columns.

LA412UL mounting dimension chart (A and B)
A B
7 in. (17.8 cm) 7 in. (17.8 cm)
8 in. (20.3 cm) 6 in. (15.2 cm)
7-1/2 in. (19.1 cm) 7-1/2 in. (19.1 cm)
6-1/2 in. (16.5 cm) 6-1/2 in. (16.5 cm)
6 in. (15.2 cm) 6 in. (15.2 cm)

Source: LiftMaster manual, 01-39383 revision B, page 11.

Position the Operator (Step 3)

The post bracket assembly can be mounted several places on the gate post.

Step 3, position the operator

  1. Open the gate to the desired open position (no greater than 100°) and hold the operator against the gate.
  2. Place the operator arm against the gate post at the desired position. Temporarily secure the gate post bracket with a clamp. The gate operator (arm) must be level.
  3. Mark mounting holes on the gate for reference. Temporarily secure the gate bracket using a clamp.
  4. Align the pull-to-open bracket to a position as CLOSE AS POSSIBLE above the screwdriver or dowel rod.
  5. Insert the hex bolt through the pull-to-open bracket and post bracket and secure with washer, lock washer and nut.

Test gate travel

If the gate does not open and close completely, adjust the position of the gate bracket and mark new mounting holes.

  1. Manually open and close the gate.
  2. Ensure that the operator does not bind against the pull-to-open bracket.
  3. Ensure that the piston does not bottom out.

Source: LiftMaster manual, 01-39383 revision B, page 12.

Secure the Brackets (Step 4)

Post bracket

The gate operator (arm) must be level.

  1. Mark holes for the post bracket. Remove the clamp and the operator, set aside.
  2. Drill adequate holes in the gate post.
  3. Secure the post bracket to the gate post using hardware.

Gate bracket

The gate operator (arm) must be level. Some installations may require additional reinforcement be installed on the gate.

  1. Drill holes in the gate (or reinforcement, if necessary) that are large enough for the gate bracket mounting hardware.
  2. Secure the gate operator to the gate using hardware (not provided).
  3. Manually move the gate to verify that it opens and closes fully.

Source: LiftMaster manual, 01-39383 revision B, page 13.

Install the Control Box (Step 5)

The control box MUST be mounted within 5 feet (1.52 m) of the gate operator. Mount the control box as high as possible for best radio reception. Make sure the control box is level.

Standard control box

  1. Remove the screws and open the control box.
  2. Select the mounting holes (according to your application) and remove the knockouts using a screwdriver and hammer.
  3. Secure the control box to the mounting surface. On a wall or column, use the provided screws (4). On a post, use U-bolts and rubber washers (not provided) to ensure a watertight seal. Make sure the U-bolts do not protrude more than 3/4 inch from the control box because this can short the control board.

Source: LiftMaster manual, 01-39383 revision B, page 14.

Large metal control box (XLSOLARCONTUL)

Wall or column mount:

  1. Open the control box. The control box door may be removed by opening the door 90°. Lift the door from the hinges and set aside until the installation is complete.
  2. Use the knock outs located at the 4 corners of the control box and knock out using a screwdriver and hammer.
  3. Secure the control box to the mounting surface using the provided screws (4).

Post mount: the post mount option is not recommended for the 33AH battery application.

  1. Open the control box. The control box door may be removed by opening the door 90°. Lift the door from the hinges and set aside until the installation is complete.
  2. The control box can be mounted to a post with 'U' bolts (refer to the chart). The knock out will accommodate a 3/8 inch diameter 'U' bolt. Select the center mounting holes (top and bottom) and knock out using a screwdriver and hammer.
  3. Secure the control box to the mounting surface with U-bolts and rubber washers (not provided) to ensure a watertight seal.

LA412UL large metal control box U-bolt opening by post type

Swipe sideways to see all columns.

LA412UL large metal control box U-bolt opening by post type
Type and size 'U' bolt opening
Standard 3 in. round pipe 3-1/2 in.
Standard 4 in. square post 4 in.
Standard 6 in. square post 6 in.

Source: LiftMaster manual, 01-39383 revision B, page 15.

Earth Ground Rod (Step 6)

  • ANY maintenance to the operator or in the area near the operator MUST NOT be performed until disconnecting the electrical power (AC or solar and battery) and locking-out the power via the operator power switch. Upon completion of maintenance the area MUST be cleared and secured, at that time the unit may be returned to service.
  • Disconnect power at the fuse box BEFORE proceeding. Operator MUST be properly grounded and connected in accordance with national and local electrical codes. NOTE: The operator should be on a separate fused line of adequate capacity.
  • ALL electrical connections MUST be made by a qualified individual.
  • DO NOT install ANY wiring or attempt to run the operator without consulting the wiring diagram.

Use the proper earth ground rod for your local area. The ground wire must be a single, whole piece of wire. Never splice two wires for the ground wire. If you cut the ground wire too short, break it, or destroy its integrity, replace it with a single wire length.

  1. Install the earth ground rod within 3 feet (.9 m) of the operator.
  2. Run wire from the earth ground rod to the operator. The earth ground wire will be connected later (see Step 11, Power Wiring).

LiftMaster notes that if the operator is not grounded properly the range of the remote controls will be reduced.

Source: LiftMaster manual, 01-39383 revision B, page 16.

Wire the Operator Arm to the Control Board (Step 7)

Step 7, wire the operator arm

  1. Choose a knockout in the bottom of the control box.
  2. Insert the operator cable through the provided watertight connector.
  3. Insert the operator cable and watertight connector into the knockout.
  4. Slide the connector nut onto the operator cable.
  5. Connect the operator cable wires to the connector according to the colored label on the connector (white to white, red to red, etc.).
  6. Plug the connector into the GATE 1 terminal on the control board as shown.
  7. Tighten the connector nut.

If installing one operator, proceed to Step 9. If installing two operators, continue with Step 8.

Source: LiftMaster manual, 01-39383 revision B, page 16.

Dual Gate Setup (Step 8)

There are two options for dual gate communication: wired or wireless. Follow the directions according to your application. Do not use wired and wireless communication simultaneously. Wired dual gate applications will have a longer battery standby time than wireless applications. Wireless dual gates will require the installation of two control boxes, one for each operator arm.

Wireless setup: activate the wireless feature

Install a second operator arm and control box by following installation steps 1 to 7.

  1. Choose an operator to be the network primary operator. All wireless accessories will need to be programmed to the primary operator. LiftMaster recommends that all accessories and board configurations are set on the primary operator.
  2. Press and release the LEARN button on the primary operator. The green XMITTER LED will light. The operator will time out of programming mode after 180 seconds.
  3. Press and release the LEARN button again on the primary operator. The yellow NETWORK LED will light.
  4. Press and release the OPEN test button to assign this operator as network primary.
  5. Press and release the LEARN button on the second operator. The green XMITTER LED will light.
  6. Press and release the LEARN button again on the second operator. The yellow NETWORK LED will light.
  7. Press and release the CLOSE test button to assign this operator as network second. Both operators will beep and the yellow NETWORK LEDs will turn off, indicating programming is successful.

Wireless setup: deactivate the wireless feature

  1. Press and release the LEARN button on either operator. The green XMITTER LED will light.
  2. Press and release the LEARN button again on the same operator. The yellow NETWORK LED will light.
  3. Press and hold the LEARN button for 5 seconds. The yellow NETWORK LED will blink (operator will beep) then turn off, indicating successful deactivation.
  4. Repeat the steps for the other operator.

Source: LiftMaster manual, 01-39383 revision B, page 17.

Wired setup: install the second arm, extension cable and junction box

Install a second operator arm by following installation steps 1 to 4. Before digging, contact local underground utility locating companies.

  1. Trench across the driveway to bury the extension cable. Use PVC conduit to prevent damage to cables.
  2. Open the junction box by removing screws (4) and set aside.
  3. Select the holes to be used for mounting and knock out using a screwdriver and hammer. Drill two holes in the junction box large enough for the watertight connectors.
  4. Mount the junction box within 3 feet (0.9 m) of the second operator.
  5. Route the operator cable and extension cable through the watertight connector nut and watertight connector.
  6. Insert the cables and watertight connectors into the holes in the junction box.
  7. Slide the connector nut onto the operator cable and extension cable.
  8. Remove the terminals from the operator cable. Connect the wires from the extension cable to the operator cable with wire nuts (strip wires and twist like colored wires together).
  9. Put the wires inside of the junction box.
  10. Secure the operator and extension cables by tightening the connector nut.
  11. Reinstall the cover.

Source: LiftMaster manual, 01-39383 revision B, page 18.

Wired setup: wire the secondary operator arm to the control board

  1. Choose a knockout in the bottom of the control box.
  2. Insert the extension cable through the watertight connector.
  3. Insert the extension cable and watertight connector into the knockout.
  4. Slide the connector nut onto the operator cable.
  5. Connect the extension cable wires to the connector according to the colored label on the connector (white to white, red to red, etc.).
  6. Plug the connector into the GATE 2 terminal on the control board as shown.
  7. Tighten the connector nut.

Set the bipart delay

Single control box. Occasionally in dual gate installations, one gate will need to open first and close second. This would happen if there was an ornamental overhang on one gate or if using a solenoid lock, for example. This gate is called the primary gate and needs to be connected to the Gate 1 connections on the control board. Thus, it is preferred that the control box be installed on the same side as this gate. If there is no appropriate location on that side for the control box, then mount the control box on the opposite side, but connect the operator closest to the control box to the Gate 2 connector and the operator on the opposite side to the Gate 1 connector. The BIPART DELAY switch on the control board needs to be set to the ON position.

Dual control boxes. The BIPART DELAY switch is used with dual control box applications and serves two functions. BIPART DELAY: used in applications where a maglock, solenoid lock, or decorative overlay would require one gate to close before the other; the control box with the BIPART DELAY switch ON will delay from the close limit when opening and be the first to close from the open limit. SYNCHRONIZED CLOSE: also used in applications where one gate travels a longer distance than the other; to synchronize the closing of the gates, set the BIPART DELAY switch to ON for both control boxes.

Source: LiftMaster manual, 01-39383 revision B, page 19.

Installing Entrapment Protection Devices (Step 9)

To prevent SERIOUS INJURY or DEATH from a moving gate:

  • ALL gate operator systems REQUIRE two independent entrapment protection systems for each entrapment zone.
  • Entrapment protection devices MUST be installed to protect anyone who may come near a moving gate.
  • Locate entrapment protection devices to protect in BOTH the open and close gate cycles.
  • Locate entrapment protection devices to protect between moving gate and RIGID objects, such as posts, walls, pillars, columns, or operator itself.

Entrapment protection MUST be installed according to the following UL 325 requirements:

  • Swing gate operators require the installation of the first external monitored entrapment protection device to function.
  • Every installation is unique. It is the responsibility of the installer to ensure that ALL entrapment zones are protected with an external monitored entrapment protection device, protecting both the open and close gate cycles.
  • LiftMaster monitored external entrapment protection devices MUST be used with LiftMaster operators to meet UL 325 requirements, see Accessories.
  • Test ALL entrapment protection devices after completing installation of the operator. For testing instructions, refer to the manual provided with your entrapment protection device.

LiftMaster's definitions:

  • ENTRAPMENT: the condition when a person is caught or held in a position that increases the risk of injury.
  • SWING GATE ENTRAPMENT ZONE: locations between a moving gate or moving, exposed operator components and a counter opposing edge or surface where entrapment is possible up to 1.8 m (6 ft) above grade. Such locations occur if during any point in travel: (a) the gap between the bottom of a moving gate and the ground is greater than 101.6 mm (4 in) and less than 406 mm (16 in); or (b) the distance between the center line of the pivot and the end of the wall, pillar, or column to which it is mounted when in the open or closed position exceeds 101.6 mm (4 in). Any other gap between a moving gate and fixed counter opposing edges or surfaces or other fixed objects is less than 406 mm (16 in) (examples are walls, curbs, berms or other immovable objects).

LiftMaster's illustrations (credited to the DASMA Gate Systems Safety Guide) show examples. See the original manual (page 20).

Source: LiftMaster manual, 01-39383 revision B, page 20.

Wiring entrapment protection devices

LiftMaster describes three options for wiring external devices, depending on the device and how it will function. Refer to the manual included with your entrapment protection device. The inputs are for monitored devices, which include pulsed photoelectric sensors, resistive edge sensors, and pulsed edge sensors. Only one monitored entrapment protection device may be wired to each input. Additional devices may be wired to the expansion board.

LA412UL entrapment protection inputs

Swipe sideways to see all columns.

LA412UL entrapment protection inputs
Board and input Device Behavior when an obstruction is sensed (LiftMaster)
Control board: CLOSE EYES/INTERRUPT (2 terminals) Close direction photoelectric sensor During gate closing the gate will open to the full open position and resets the Timer-to-Close. The input is disregarded during gate opening.
Control board: CLOSE EDGE (2 terminals) Close direction edge sensor During gate closing the gate will reverse to the full open position, disengaging the Timer-to-Close. The input is disregarded during gate opening.
Control board: OPEN EYES/EDGE (2 terminals) Open direction photoelectric sensor or edge sensor During gate opening the gate will reverse for 4 seconds then stop. The input is disregarded during gate closing.
Expansion board: EYE ONLY and COM Open or close direction photoelectric sensors Based on the switch next to the terminals. Switch set to CLOSE: gate reverses fully. Switch set to OPEN: gate reverses 4 seconds.
Expansion board: EYE/EDGE and COM (two inputs) Open or close direction photoelectric sensors or edge sensor Based on the switch next to the terminals. Switch set to CLOSE: gate reverses fully. Switch set to OPEN: gate reverses 4 seconds.

Source: LiftMaster manual, 01-39383 revision B, page 21.

Install Solar Panels (Step 10)

The LA412UL runs from solar power only. Solar panels are not listed in LiftMaster's carton illustration; the standard control box parts list on page 46 includes a 10W solar panel (SP10W12V) and the 29-NP712 battery. See Accessories for the solar panel kit (SP10W12V and SP20W12V; 30W maximum for 12 Vdc operators and a 33AH battery harness requirement).

Solar zones

Solar panel recommendations are based upon the average solar radiation and the temperature effects on batteries in the given zones as shown on the map in the manual (page 22). Local geography and weather conditions may require additional solar panels. Solar powered gate operator installations are not supported in northern climates due to cold weather and a reduced number of hours of sunlight during the winter months. The cycles/day ratings are approximations. Ratings vary based on gate construction, installation, and temperature. Solar panels cannot be installed in areas that experience long periods of heavy fog, lake effect snow, or rain.

Source: LiftMaster manual, 01-39383 revision B, page 22.

Solar usage guide

LA412UL typical system standby battery current consumption (mA), as printed by LiftMaster (page 23)

Swipe sideways to see all columns.

LA412UL typical system standby battery current consumption (mA), as printed by LiftMaster (page 23)
Feature Current draw
Main board with no radios programmed 2.7 mA
One or more LiftMaster remote controls programmed +1 mA
myQ device or wireless dual gate programmed +2.4 mA
Expansion board +11.1 mA
Per loop detector LOOPDETLM (up to 3 loop detectors can be plugged in to the expansion board) +3.8 mA

Documentation note. The heading of this table on page 23 reads "System voltage 24V," but the LA412UL is a 12 Vdc operator (page 7). Page 31 also gives a "critically low battery" level of 23 V, and the control board accessory power row on page 34 says 24 VDC, while the specifications give 12 Vdc, 500 mA. These values appear to be carried over from LiftMaster's 24 Vdc operators; confirm the correct figures with LiftMaster before relying on them.

Add up current draw by feature and accessory to determine total current draw. LiftMaster states that the use of photoelectric sensor heaters (models LMRRUL and LMTBUL) is NOT recommended in solar applications. For single and dual gate cycles per day by zone, panel wattage (10W, 20W, or 30W, which is three 10W 12V panels in parallel), battery size (7AH or 33AH), and battery current draw (6 to 200 mA), see the cycles-per-day tables on page 23 of the manual. LiftMaster states that all numbers are estimates and actual results may vary.

Position and installation

The location of the panel(s) is critical to the success of the installation. In general, the panel(s) should be mounted using the provided angle bracket facing due south. The solar panel(s) should be mounted in an area clear of all obstructions and shade from buildings and trees. If the panel(s) is not casting a shadow, the battery is not being charged. Tall trees or buildings that do not shade the solar panel(s) in the summer could shade the solar panel(s) during the winter months when the sun sits lower in the sky. Solar panel(s) MUST be installed facing south; use a compass to determine direction. LiftMaster's general instructions (your installation may vary slightly depending on the solar panel purchased):

  1. Position the mounting bracket on the mounting surface. Mark and drill holes.
  2. Secure the solar panel to the mounting bracket using the hex bolts, hex nuts and washers provided.
  3. Secure the solar panel to the mounting surface using lag screws provided.

Source: LiftMaster manual, 01-39383 revision B, page 24.

Power Wiring (Step 11)

LiftMaster's Step 11 shows how to wire the batteries and wire the solar panels in drawings on page 25 of the manual; this page does not reproduce them. The operator has no AC power connection (the main AC supply is listed as "N/A - Solar Only"). All control wiring used to connect external devices to Class 2 circuits of the operator must be (QPTZ) Power-Limited Circuit Cables, Type CL2, CL2P, CL2R, or CL2X or other cable with equivalent or better electrical, mechanical, and flammability ratings.

Source: LiftMaster manual, 01-39383 revision B, page 25.

Finish Installation (Step 12)

Finish the installation

  1. Turn the release lever clockwise 180° back to the engaged position. This engages the motor.
  2. Turn the key clockwise 180°. This locks the release lever. The operator is now engaged.
  3. Fasten warning signs to the gate with cable ties. Warning signs MUST be installed on both sides of the gate and in plain view.

Documentation note. The table of contents lists this as Step 12, but the heading on page 26 reads "Step 11 Finish Installation" (Step 11 on page 25 is Power Wiring).

Source: LiftMaster manual, 01-39383 revision B, page 26.

Back to contents

LiftMaster LA412UL Wiring

LiftMaster LA412UL Wiring Diagram

LiftMaster's installation manual shows the standard control box wiring diagram on page 47 (document 01-39383 revision B). This page does not reproduce the diagram; use the original LiftMaster manual for terminal-level connections. See Original LiftMaster Documentation.

  • To protect against fire and electrocution: DISCONNECT power (AC or solar and battery) BEFORE installing or servicing operator.
  • For continued protection against fire: replace ONLY with a fuse of the same type and rating.

Source: LiftMaster manual, 01-39383 revision B, page 47.

Wiring Accessories to the LA412UL Control Board

All control wiring used to connect external devices to Class 2 circuits of the operator must be (QPTZ) Power-Limited Circuit Cables, Type CL2, CL2P, CL2R, or CL2X or other cable with equivalent or better electrical, mechanical, and flammability ratings. LiftMaster describes these control board inputs and outputs (pages 34 and 35):

LA412UL control board inputs and outputs

Swipe sideways to see all columns.

LA412UL control board inputs and outputs
Input / output Terminals Function (LiftMaster) Manual page
EXIT 2 terminals Soft open command (maintained switch does not override external safeties and does not reset alarm condition). Used for exit probe, telephone entry, external exit loop detector, or any device that would command the gate to open. Opens a closing gate and holds open an open gate; if maintained, pauses Timer-to-Close at OPEN limit. 31
SHADOW 2 terminals Used for an external shadow loop detector when the loop is positioned under the swing of the gate. Holds open gate at open limit; only active when the gate is at the OPEN limit, disregarded at all other times; pauses Timer-to-Close at OPEN limit. 31
INTERRUPT 2 terminals Used for photoelectric sensors and an external interrupt loop detector when the loop is on the outside of the gate. Holds open gate at open limit; stops and reverses a closing gate to open limit; pauses Timer-to-Close at OPEN limit; activates quick close and anti-tailgate features when enabled on the expansion board. 31
Maglock (LOCK) 2 terminals, N.C. and COM Relay contact output, normally closed (N.C.) output for maglocks. The relay activates prior to motor activation and during motor run. The relay is off when the motor is off. 32
Single button control (SBC) 2 terminals Gate command sequence: open, stop, close, stop, and so on. Soft open (maintained switch does not override external safeties and does not reset alarm condition). 32
Fire department open input 2 terminals Acts as a hard open. A maintained input overrides (ignores) external safeties (photoelectric sensor and edge) and pauses Timer-to-Close. A momentary input logic works as single button control, safeties remain active, and Timer-to-Close is re-enabled. 32
Accessory power, 24 VDC, MAX 500 mA (as printed; see note below) 4 terminals SWITCHED: switched ON with gate motion and at the open limit when Timer-to-Close is active; turns off 5 seconds after motion. UNSWITCHED: 24 Vdc voltage out to power accessories, always ON. 32

Documentation note. The accessory power row of this table (page 34) says 24 VDC, while the operator specifications on page 7 give 12 Vdc, 500 mA max. for accessory power. Confirm the voltage with LiftMaster before connecting accessories.

Entrapment protection devices are wired as described in Wiring entrapment protection devices (page 21). Per the specifications, the optional expansion board (Model K1D8387-1CC) adds inputs for additional entrapment protection devices and controls; see Accessories.

Source: LiftMaster manual, 01-39383 revision B, pages 34 to 35.

Back to contents

LiftMaster LA412UL Adjustment

Limit and Force Adjustment

To reduce the risk of SEVERE INJURY or DEATH:

  • Without a properly installed safety reversal system, persons (particularly small children) could be SERIOUSLY INJURED or KILLED by a moving gate.
  • Too much force on the gate will interfere with proper operation of the safety reversal system.
  • NEVER increase force beyond the minimum amount required to move the gate.
  • NEVER use force adjustments to compensate for a binding or sticking gate.
  • If one control (force or travel limits) is adjusted, the other control may also need adjustment.
  • After ANY adjustments are made, the safety reversal system MUST be tested. The gate MUST reverse on contact with an object.

The operator is designed with electronic controls to make travel limit and force adjustments easy. The adjustments allow you to program where the gate will stop in the open and close position. The electronic controls sense the amount of force required to open and close the gate. The force is adjusted automatically when you program the limits but should be fine tuned using the REVERSAL FORCE dial on the control board to compensate for environmental changes. The limit setup LEDs (next to the SET OPEN and SET CLOSE buttons) indicate the status of the limits. The limits can be set using the control board or a remote control (see Limit Setup with a Remote Control); setting the limits with a remote control requires a 3-button remote control programmed to OPEN, CLOSE, and STOP. The TEST buttons on the control board will not work until the limits have been set and the required entrapment protection devices are installed.

LA412UL limit setup LEDs

Swipe sideways to see all columns.

LA412UL limit setup LEDs
SET OPEN LED SET CLOSE LED Operator mode Explanation (LiftMaster)
OFF OFF NORMAL MODE Limits are set
BLINKING BLINKING LIMIT SETTING MODE Limits are not set
BLINKING ON LIMIT SETTING MODE Open limit is not set
ON BLINKING LIMIT SETTING MODE Close limit is not set
ON ON LIMIT SETTING MODE Limits are set

Initial limits and force adjustments (control board)

For dual gate applications the limits will have to be set for each operator. The gate MUST be attached to the operator before setting the limits and force. If a mistake is made while programming the limits, press the reset button to start over.

  1. Set the GATE switch to the 1 position.
  2. Press and release the SET OPEN and SET CLOSE buttons simultaneously to enter limit setting mode.
  3. Press and hold the MOVE GATE buttons to move the gate to the open or close limit.
  4. Press and release the SET CLOSE or SET OPEN button depending on which limit is being set.
  5. Press and hold the MOVE GATE button to move the gate to the other limit.
  6. Press and release the SET CLOSE or SET OPEN button depending on which limit is being set. The operator will exit limit setting mode.*
  7. Cycle the gate open and close using the TEST BUTTONS. This automatically sets the force.
  8. For dual gates, set the GATE switch to the 2 position and repeat steps 2 to 7.

When the limits are set properly the operator will automatically exit limit setting mode. *Dual gates only: when the limits are set on the secondary gate first, the control board will not exit the limit setting mode until the limits are set on the primary gate.

Source: LiftMaster manual, 01-39383 revision B, pages 26 to 27.

Fine tune the force

Once the initial limits have been set, the REVERSAL FORCE dial on the control board is used for fine tuning the force where wind or environmental changes may affect the gate travel. The dial is set to minimum at the factory. Based on the length and weight of the gate it may be necessary to make additional force adjustments. The force setting should be high enough that the gate will not reverse by itself nor cause nuisance interruptions, but low enough to prevent serious injury to a person. The force setting is the same for both the open and close gate directions.

  1. Open and close the gate with the TEST BUTTONS.
  2. If the gate stops or reverses before reaching the fully open or closed position, increase the force by turning the force control slightly clockwise.
  3. Perform the "Obstruction Test" after every limit and force setting adjustment.

Adjust the limits. After both limits are set and the operator is ready to run, one limit can be adjusted independently from the other by following steps 1 to 3 of the initial limits and force adjustment procedure.

Obstruction test

The operator is equipped with an inherent (built into the operator) obstruction sensing device. If the gate encounters an obstruction during motion, the operator will reverse direction of the gate and then stop. This procedure tests ONLY the inherent obstruction sensing device:

  1. Open and close the gate with the TEST BUTTONS, ensuring that the gate is stopping at the proper open and close limit positions.
  2. Place an object between the open gate and a rigid structure. Make sure that any external entrapment protection devices will NOT be activated by the object.
  3. Run the gate in the close direction. The gate should stop and reverse upon contact with the object. If the gate does not reverse off the object, reduce the force setting by turning the force control slightly counter-clockwise. The gate should have enough force to reach both the open and close limits, but MUST reverse after contact with an object.
  4. Repeat the test for the open direction.

Test the operator after any adjustments are made.

Source: LiftMaster manual, 01-39383 revision B, page 28.

Limit Setup with a Remote Control

To set the limits using a remote control, you first need a 3-button remote control that has been programmed for OPEN, CLOSE, and STOP (see How to Program a Remote Control). For dual gate applications the limits will have to be set for each operator. The gate MUST be attached to the operator before setting the limits and force. Ensure the gate is closed.

Initial limits and force adjustment

  1. Press and release the SET OPEN and SET CLOSE buttons simultaneously to enter limit setting mode.
  2. Press and hold the OPEN or CLOSE button on the remote control until the gate reaches the desired open position. The gate can be jogged back and forth using the OPEN and CLOSE buttons on the remote control.
  3. Once the gate is in the desired open position, press and release the STOP button on the remote control.
  4. Press and release the OPEN button on the remote control again to set the open limit.
  5. Press and hold the CLOSE or OPEN button on the remote control until the gate reaches the desired close position. The gate can be jogged back and forth using the OPEN and CLOSE buttons.
  6. Once the gate is in the desired close position, press and release the STOP button on the remote control.
  7. Press and release the CLOSE button on the remote control again to set the close limit.
  8. Cycle the gate open and close. This automatically sets the force.

Set the close limit only

  1. Press and release the SET OPEN and SET CLOSE buttons simultaneously to enter limit setting mode.
  2. Press and hold the CLOSE button on the remote control until the gate reaches the desired close position. The gate can be jogged back and forth using the OPEN and CLOSE buttons.
  3. Once the gate is in the desired close position, press and release the STOP button on the remote control.
  4. Press and release the CLOSE button on the remote control again to set the close limit. When the close limit is set properly the operator will automatically exit limit setting mode.

LiftMaster's page 45 also describes setting the open limit only in the same way, using the OPEN button; see the original manual.

Source: LiftMaster manual, 01-39383 revision B, page 45.

Back to contents

LiftMaster LA412UL Programming

How to Program a Remote Control

A total of 50 Security+ 2.0 remote controls or KPW250 keypads and 2 keyless entries (1 PIN for each keyless entry) can be programmed to the operator. When programming a third keyless entry to the operator, the first keyless entry will be erased to allow the third keyless entry to be programmed. When the operator's memory is full it will exit the programming mode and the remote control will not be programmed; the memory will need to be erased before programming any additional remote controls. If installing an 86LM to extend the range of the remote controls DO NOT straighten the antenna.

There are 3 different options for programming the remote control, depending on how you would like the remote control to function:

Single button as OPEN only

  1. Press and release the LEARN button (operator will beep and green XMITTER LED will light). The operator will time out of programming mode after 30 seconds.
  2. Press the OPEN button.
  3. Press the remote control button that you would like to program.

Single button (SBC) as OPEN, CLOSE, and STOP

  1. Press and release the LEARN button (operator will beep and green XMITTER LED will light). The operator will time out of programming mode after 30 seconds.
  2. Press the remote control button that you would like to program.

Three separate buttons as OPEN, CLOSE, and STOP

  1. Press and release the LEARN button (operator will beep and green XMITTER LED will light). The operator will time out of programming mode after 30 seconds.
  2. Press the OPEN, CLOSE, or STOP button, depending on the desired function.
  3. Press the remote control button that you would like to program.

The operator will automatically exit learn mode (operator will beep and green XMITTER LED will go out) if programming is successful. To program additional Security+ 2.0 remote controls or remote control buttons, repeat the programming steps above.

Source: LiftMaster manual, 01-39383 revision B, page 29.

How to Connect the LA412UL to the LiftMaster Internet Gateway

The LiftMaster Internet Gateway is not provided. LiftMaster describes two ways to program the operator to the gateway.

Using the LEARN button on the operator's control board

  1. Connect the ethernet cable to the LiftMaster Internet Gateway and the router.
  2. Connect power to the LiftMaster Internet Gateway.
  3. Create an online account by visiting www.myliftmaster.com.
  4. Register the LiftMaster Internet Gateway.
  5. Use an internet enabled computer or smartphone to add devices. The LiftMaster Internet Gateway will stay in learn mode for three minutes.
  6. Press the LEARN button twice on the primary operator (the operator will beep as it enters learn mode).

The LiftMaster Internet Gateway will pair to the operator if it is within range and the operator will beep if programming is successful.

Using the reset button on the operator

  1. Connect the ethernet cable to the LiftMaster Internet Gateway and the router.
  2. Connect power to the LiftMaster Internet Gateway.
  3. Create an online account by visiting www.myliftmaster.com.
  4. Register the LiftMaster Internet Gateway.
  5. Use an internet enabled computer or smartphone to add devices. The LiftMaster Internet Gateway will stay in learn mode for three minutes.
  6. Ensure the gate is closed.
  7. Give the operator an OPEN command.
  8. Within 30 seconds, when the gate is at the open limit, press and release the reset button 3 times (on the primary gate) to put the primary operator into High Band Learn Mode (the operator will beep as it enters learn mode).

The LiftMaster Internet Gateway will pair to the operator if it is within range and the operator will beep if programming is successful. The status shown by the LiftMaster Internet Gateway app will be either "open" or "closed." The gate operator can then be controlled through the LiftMaster Internet Gateway app.

Source: LiftMaster manual, 01-39383 revision B, page 30.

All Security Equipment note. The LiftMaster Internet Gateway (Model 828LM) is a separate accessory. See the LiftMaster Internet Gateway 828LM product page for current availability.

Constant Pressure Override and Erase Procedures

Constant Pressure Override (CPO)

Constant Pressure Override is for use with KPW5 and KPW250 keypads (not provided). The KPW5/KPW250 wireless commercial keypads are security keypads and can only be programmed to ONE gate operator (see the KPW5/KPW250 manual for complete programming instructions). The feature is intended to temporarily override a fault in the entrapment protection system, in order to operate the gate until the external entrapment protection device is realigned or repaired. Use the feature only in line of sight of the gate when no obstructions to travel are present. External entrapment protection devices include LiftMaster monitored photoelectric sensors and LiftMaster monitored wired and wireless edge sensors. Be sure to repair or replace these devices promptly if they are not working properly.

  1. Enter a valid 4-digit PIN.
  2. Press and hold # for 5 seconds to enter CPO. Continue to hold # to keep the operator in motion. A continuous tone will sound until the limit is met and/or # is released.
  3. The operator will stop when either the operator reaches a limit or the user releases #.

Erase all codes

  1. Press and release the LEARN button (operator will beep and green XMITTER LED will light).
  2. Press and hold the LEARN button again until the green XMITTER LED flashes and then release the button (approximately 6 seconds). All remote control codes are now erased.

Erase limits

  1. To erase the limits, press and hold the SET OPEN and SET CLOSE buttons simultaneously (5 seconds) until both the SET OPEN and SET CLOSE LEDs blink rapidly and the operator beeps.
  2. Release the buttons and the SET OPEN and SET CLOSE LEDs will blink slowly, indicating the limits will need to be set.

Remove and erase monitored entrapment protection devices

  1. Remove the entrapment protection device wires from the terminal block.
  2. Press and release the SET OPEN and SET CLOSE buttons simultaneously. The SET OPEN and SET CLOSE LEDs will turn on (entering learn limit mode).
  3. Press and release both the SET OPEN and SET CLOSE buttons again to turn off the SET OPEN and SET CLOSE LEDs (exiting learn limit mode).

Source: LiftMaster manual, 01-39383 revision B, page 30.

Back to contents

LiftMaster LA412UL Operation

LA412UL Control Board Overview

LiftMaster identifies these control board features (numbers match the manual's callouts on page 31):

  1. SET OPEN button: sets the OPEN limit (see Limit and Force Adjustment).
  2. SET CLOSE button: sets the CLOSE limit.
  3. MOVE GATE buttons: open or close the gate when the operator is in limit setting mode.
  4. BATT FAIL: when AC power is OFF and battery voltage is critically low the gate will latch at a limit until AC power is restored or battery voltage increases. The option select switch set to OPEN forces the gate to automatically open and then latch at the OPEN limit until AC power is restored or battery voltage increases. The option select switch set to CLOSE forces the gate to latch at the CLOSE limit if at the CLOSE limit or on the next CLOSE command until AC power is restored or battery voltage increases. Constant pressure on a hard command input overrides to open or close the gate. Critically low battery is less than 23 V.
  5. BIPART DELAY switch: the LOCK/BIPART DELAY switch is used only for dual gates (see Set the bipart delay).
  6. LEARN button: used for programming remote controls and the network.
  7. TIMER-TO-CLOSE (TTC) dial: can be set to automatically close the gate after a specified time period. The TTC is factory set to OFF. If the TTC is set to OFF, the gate will remain open until the operator receives another command from a control. Rotate the dial to the desired setting; the range is 0 to 180 seconds, and 0 seconds is OFF. Any radio command, single button control, or CLOSE command on the control board before the TTC expires will close the gate. The TTC is reset by any signals from the open controls, loops, close edges, and close photoelectric sensors (IRs).
  8. REVERSAL FORCE dial: fine tunes the force (see fine tune the force).
  9. TEST BUTTONS: operate the gate (OPEN, STOP and CLOSE).
  10. STATUS LEDs: indicate the status of the operator (see the Control Board LEDs).
  11. DIAGNOSTICS display: shows the operator type, firmware version, and codes. The operator type displays as "LA" followed by a "40", which indicates the operator type as LA412DC. The firmware version shows after the operator type (example "1.2"). See Diagnostic Codes.

Source: LiftMaster manual, 01-39383 revision B, page 31.

Manual Release

In case of a power failure, the operator can be disengaged from the gate. LiftMaster notes that the release action may sometimes feel stiff or jerky, which is normal and has no effect on function. It is also normal for the operator to run slow right after a disconnect or complete loss of AC/battery power (the operator will need to run a complete open and close cycle).

Release (manual mode)

  1. Insert the key into the lock.
  2. Turn the key counter-clockwise 180°.
  3. Turn the release lever counter-clockwise 180°. The operator is in manual mode and the gate can be opened and closed manually.

The lock relay will activate then turn off after 2 minutes to conserve power.

Engage

  1. Turn the release lever clockwise 180°. This engages the motor.
  2. Turn the key clockwise 180°. This locks the release lever.
  3. Remove the key and store it in a safe place. The operator is now engaged.

Use the manual release ONLY when the gate is not moving.

Source: LiftMaster manual, 01-39383 revision B, page 32.

LA412UL Reset Button

The reset button is located on the side of the control box and serves several functions (LiftMaster, page 32):

  • Press the reset button to stop a moving gate during a normal open/close cycle, like a stop button.
  • Press the reset button once while the gate is in the open position to disable the Timer-to-Close. The gate will stay in the open position. To restart the Timer-to-Close, either press the reset button or activate the gate with a programmed remote control.
  • Press the reset button to shut off the alarm and reset the operator.

Source: LiftMaster manual, 01-39383 revision B, page 32.

Party Mode

Press the reset button once while the gate is in the open position to disable the Timer-to-Close; the gate will stay in the open position. To restart the Timer-to-Close, either press the reset button or activate the gate with a programmed remote control. Party mode can also be enabled from a KPW5 or KPW250 keypad (not provided):

  1. Enter a valid 4-digit PIN when the gate is at the open limit and the timer is running.
  2. The operator will chirp, indicating the timer is canceled.

To restart the gate, either re-enter the 4-digit PIN or activate a hard input or a programmed remote.

Source: LiftMaster manual, 01-39383 revision B, page 32.

LA412UL Operator Alarm

If a contact sensor detects an obstruction twice consecutively, the alarm will sound (up to 5 minutes) and the operator will need to be reset. When the inherent force of the operator (RPM/current sensor) detects any of the following twice consecutively, the alarm will sound (up to 5 minutes) and the operator will need to be reset:

  • The operator arm or gate is incorrectly installed.
  • The gate does not meet specifications.
  • Gate hinges are too tight or broken and the gate is not moving freely.
  • The gate is moving and a car pushes the gate.
  • A foreign object is on the gate frame while the gate is moving.
  • The gate hits the driveway or curb and gets stuck or bent in an awkward position.
  1. Remove any obstructions.
  2. Press the reset button to shut off the alarm and reset the operator.

After the operator is reset, normal functions will resume. The operator alarm will beep 3 times with a command if the battery is low (see battery problems).

Source: LiftMaster manual, 01-39383 revision B, page 33.

LA412UL Remote Control Operation

Single button control (SBC) functionality. Once the remote control has been programmed, the operator will operate as follows: when the gate is in the closed position, activation of the remote control button will open the gate. During the open cycle another activation of the remote control will stop the gate and the next activation of the remote control will close the gate. When the gate is in the open position, activation of the remote control button will close the gate. If the remote control is activated while the gate is closing, the gate will stop and the next activation will open the gate. See How to Program a Remote Control for the other programming options.

Source: LiftMaster manual, 01-39383 revision B, page 33.

Back to contents

LiftMaster LA412UL Troubleshooting

This section follows the troubleshooting chart in LiftMaster's LA412UL installation manual (document 01-39383 revision B). The full chart below keeps LiftMaster's wording; the problem-specific sections after it restate rows of the chart in task order and are condensed. Disconnect power (AC or solar and battery) before servicing the operator, and replace a fuse only with one of the same type and rating.

Documentation note. In the chart row "Gate opens, but will not close with transmitter or Timer-to-Close" (page 39), the possible causes are lettered a to e (five items) but the recommended actions are lettered a to g (seven items), so the letters do not correspond beyond the first two. The chart below shows both lists exactly as printed.

LiftMaster LA412UL Troubleshooting Chart

LiftMaster LA412UL troubleshooting chart (letters in each row correspond except where the documentation note says otherwise)

Swipe sideways to see all columns.

LiftMaster LA412UL troubleshooting chart (letters in each row correspond except where the documentation note says otherwise)
Symptom Possible causes Recommended diagnostic action Manual reference
Operator does not run and diagnostic display not on.
  1. No power to control board.
  2. Open fuse.
  3. If on battery power only, low or dead batteries.
  4. Defective control board.
  1. Check AC and battery power.
  2. Check fuses.
  3. Charge batteries by AC or solar power or replace batteries.
  4. Replace defective control board.
Troubleshooting Chart, page 38
Control board powers up, but motor does not run.
  1. Reset switch is stuck.
  2. Stop button active or jumper not in place for stop circuit.
  3. If on battery power only, low or dead batteries.
  4. Open or Close input active.
  5. Entrapment Protection Device active.
  6. Vehicle loop detector or probe active.
  7. Defective control board.
  1. Check reset switch.
  2. Check Stop button is not "stuck on", or verify that the stop button is a normally closed circuit, or put a jumper on the stop circuit.
  3. Charges batteries by AC or solar power or replace batteries.
  4. Check all Open and Close inputs for a "stuck on" input.
  5. Check all Entrapment Protection Device inputs for a "stuck on" sensor.
  6. Check all vehicle detector inputs for a "stuck on" detector.
  7. Replace defective control board.
Troubleshooting Chart, page 38
Arm moves, but cannot set correct limits.
  1. Arm does not extend or retract enough during travel.
  2. Arm is interfering with mounting bracket.
  3. Gate is too difficult to move.
  1. Disengage the arm and ensure arm moves freely.
  2. Examine the hinge point where the arm mounts to the gate post. Make sure that the arm housing does not hit or interfere with the gate post or mounting bracket. Correct as necessary.
  3. Disconnect arm from gate and move gate manually. Gate must move easily and freely through its entire range, limit-to-limit. Repair gate as needed.
Troubleshooting Chart, page 38
Gate does not fully open or fully close when setting limits.
  1. Arm does not extend or retract enough during travel.
  2. Arm is interfering with mounting bracket.
  3. Gate is too difficult to move.
  1. Disengage the arm and ensure arm moves freely.
  2. Examine the hinge point where the arm mounts to the gate post. Make sure that the arm housing does not hit or interfere with the gate post or mounting bracket. Correct as necessary.
  3. Remove arm from gate and move gate manually. Gate must move easily and freely through its entire range, limit-to-limit. Repair gate as needed.
Troubleshooting Chart, page 38
Operator does not respond to a wired control/command (example: Open, Close, SBC, etc.)
  1. Check Open and Close command input LEDs.
  2. Stop button is active.
  3. Reset button is stuck.
  4. If on battery power only, low or dead batteries.
  5. Entrapment Protection Device active.
  6. Vehicle loop detector or vehicle probe active.
  1. Check all Open and Close inputs for a "stuck on" input.
  2. Check Stop button is not "stuck on".
  3. Check Reset button.
  4. Charges batteries by AC or solar power or replace batteries.
  5. Check all Entrapment Protection Device inputs for a "stuck on" sensor.
  6. Check all vehicle detector inputs for a "stuck on" detector.
Troubleshooting Chart, page 38
Operator does not respond to a wireless control or transmitter
  1. Check XMITTER LED when wireless control is active.
  2. Stop button is active.
  3. Reset button is stuck.
  4. Poor radio reception.
  1. Activate wireless control and check XMITTER LED is on. Re-learn wireless control/transmitter to control board. Replace wireless control as needed.
  2. Check Stop button is not "stuck on".
  3. Check Reset button.
  4. Check if similar wired control operates correctly. Check if wireless controls works properly when within a few feet of operator. Check operator's antenna and antenna wire. Check other wireless controls or devices.
Troubleshooting Chart, page 38
Gate stops during travel and reverses immediately.
  1. Control (Open, Close) becoming active.
  2. Vehicle loop detector active.
  3. Low battery voltage.
  1. Check all Open and Close inputs for an active input.
  2. Check all vehicle detector inputs for an active detector.
  3. Battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.
Troubleshooting Chart, page 38
Gate opens, but will not close with transmitter or Timer-to-Close.
  1. Open control active.
  2. Vehicle loop detector active.
  3. Fire Dept input active.
  4. Timer-to-Close not set.
  5. Close Entrapment Protection Device active.
  1. Check all Open inputs for an active input.
  2. Check all vehicle detector inputs for an active detector.
  3. Check AC power and AC Fail option setting.
  4. Check if AC power is available. If no AC power, then running on batteries and battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.
  5. Check Fire Dept input.
  6. Check Timer-to-Close (TTC) setting.
  7. Check all Entrapment Protection Device inputs for an active sensor.
Troubleshooting Chart, page 39
Gate closes, but will not open.
  1. Vehicle loop detector active.
  2. Low battery with LOW BATT option set to CLOSE.
  1. Check all vehicle detector inputs for an active detector.
  2. Check if AC power is available. If no AC power, then running on batteries and battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.
Troubleshooting Chart, page 39
Exit loop activation does not cause gate to open.
  1. Exit vehicle detector setup incorrectly.
  2. Defective Exit loop detector.
  3. Low battery with LOW BATT option set to CLOSE.
  1. Review Exit loop detector settings. Adjust settings as needed.
  2. Replace defective Exit loop detector.
  3. Check if AC power is available. If no AC power, then running on batteries and battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.
Troubleshooting Chart, page 39
Interrupt loop does not cause gate to stop and reverse.
  1. Vehicle detector setup incorrectly.
  2. Defective vehicle loop detector.
  1. Review Interrupt loop detector settings. Adjust settings as needed.
  2. Replace defective Interrupt loop detector.
Troubleshooting Chart, page 39
Shadow loop does not keep gate at open limit.
  1. Vehicle detector setup incorrectly.
  2. Defective vehicle loop detector.
  1. Review Shadow loop detector settings. Adjust settings as needed.
  2. Replace defective Shadow loop detector.
Troubleshooting Chart, page 39
Obstruction in gate's path does not cause gate to stop and reverse.
  1. Force adjustment needed.
  1. Refer to the Adjustment section to conduct the obstruction test and perform the proper force adjustment that is needed.
Troubleshooting Chart, page 39
Photoelectric sensor does not stop or reverse gate.
  1. Incorrect photoelectric sensor wiring.
  2. Defective photoelectric sensor.
  1. Check photoelectric sensor wiring. Retest that obstructing photoelectric sensor causes moving gate to stop, and may reverse direction.
  2. Replace defective photoelectric sensor. Retest that obstructing photoelectric sensor causes moving gate to stop, and may reverse direction.
Troubleshooting Chart, page 39
Edge Sensor does not stop or reverse gate.
  1. Incorrect edge sensor wiring.
  2. Defective edge sensor.
  1. Check edge sensor wiring. Retest that activating edge sensor causes moving gate to stop and reverse direction.
  2. Replace defective edge sensor. Retest that activating edge sensor causes moving gate to stop and reverse direction.
Troubleshooting Chart, page 39
Alarm sounds for 5 minutes or alarm sounds with a command.
  1. Double entrapment occurred (two obstructions within a single activation).
  1. Check for cause of entrapment (obstruction) detection and correct. Press the reset button to shut off alarm and reset the operator.
Troubleshooting Chart, page 39
Alarm beeps three times with a command.
  1. Low battery.
  1. Check if AC power is available. If no AC power, then running on batteries and battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.
Troubleshooting Chart, page 39
On dual-gate system, incorrect gate opens first or closes first.
  1. Incorrect Bipart switch setting.
  1. Change setting of both operator's Bipart switch settings. One operator should have Bipart switch ON (operator that opens second) and the other operator should have Bipart switch OFF (operator that opens first).
Troubleshooting Chart, page 39
Alarm beeps when running.
  1. Expansion board setting.
  2. Constant pressure to open or close is given.
  1. Pre-warning is set to "ON".
  2. Constant pressure to open or closed is given.
Troubleshooting Chart, page 39
Expansion board function not controlling gate.
  1. Defective main board to expansionboard wiring.
  2. Incorrect input wiring to expansion board.
  3. Defective expansion board or defective main board.
  1. Check main board to expansion board wiring. If required, replace wire cable.
  2. Check wiring to all inputs on expansion board.
  3. Replace defective expansion board or defective main board.
Troubleshooting Chart, page 40
Maglock not working correctly.
  1. Maglock wired incorrectly.
  1. Check that Maglock is wired to N.C. and COM terminals. Check that Maglock has power (do not power maglock from control board accessory power terminals). If shorting lock's NO and COM wires does not activate Maglock, then replace Maglock or Maglock wiring (refer to Wiring Diagrams).
Troubleshooting Chart, page 40
Solenoid lock not working correctly.
  1. Solenoid wired incorrectly.
  1. Check that Solenoid is wired to N.O. and COM terminals. Check that Solenoid has power (do not power solenoid from control board accessory power terminals). If shorting lock's NC and COM wires does not activate Solenoid, then replace Solenoid lock or Solenoid wiring (refer to Wiring Diagrams).
Troubleshooting Chart, page 40
Switched (SW) Accessory power remaining on.
  1. In limit setup mode.
  1. Learn the limits.
Troubleshooting Chart, page 40
Accessories connected to Switch (SW) Accessory power not working correctly, turning off, or resetting.
  1. Normal behavior.
  1. Move accessory to accessory power "ON".
Troubleshooting Chart, page 40
Accessories connected to Accessory power not working correctly, turning off, or resetting.
  1. Accessory power protector active.
  2. Defective control board.
  1. Disconnect all accessory powered devices and measure accessory power voltage (should be 23 – 30 Vdc). If voltage is correct, connect accessories one at a time, measuring accessory voltage after every new connection.
  2. Replace defective control board.
Troubleshooting Chart, page 40
Quick Close not working correctly.
  1. Quick Close setting incorrect.
  2. Interrupt loop detector.
  3. Defective Expansion board.
  1. Check that Quick Close setting is ON.
  2. Check operation of Interrupt Loop detector.
  3. Replace defective Expansion board.
Troubleshooting Chart, page 40
Anti-Tailgating not working correctly.
  1. Anti-Tail setting incorrect.
  2. Interrupt loop detector.
  3. Defective Expansion board.
  1. Check that Anti-Tail setting is ON.
  2. Check operation of Interrupt Loop detector.
  3. Replace defective Expansion board.
Troubleshooting Chart, page 40
AUX Relay not working correctly.
  1. AUX Relay setting incorrect.
  2. AUX Relay wiring incorrect.
  3. Defective Expansion board.
  1. Check AUX Relay switches settings.
  2. Check that wiring is connected to either N.O. and COM or to N.C. and COM.
  3. Set AUX Relay to another setting and test. Replace defective expansion board.
Troubleshooting Chart, page 40
Solar operator not getting enough cycles per day.
  1. Insufficient panel wattage.
  2. Excessive accessory power draw.
  3. Old batteries.
  4. Solar panels are not getting enough sunlight.
  1. Add more solar panels.
  2. Reduce the accessory power draw by using LiftMaster low power accessories.
  3. Replace batteries.
  4. Relocate the solar panels away from obstructions (trees, buildings, etc.).
Troubleshooting Chart, page 40
Solar operator, insufficient standby time.
  1. Insufficient panel wattage.
  2. Excessive accessory power draw.
  3. Battery capacity too low.
  1. Add more solar panels.
  2. Reduce the accessory power draw by using LiftMaster low power accessories.
  3. Use batteries with higher amp hour (AH) rating.
Troubleshooting Chart, page 40

Source: LiftMaster manual, 01-39383 revision B, pages 38 to 40.

Gate Will Not Open or the LiftMaster LA412UL Does Not Move

If a LiftMaster LA412UL gate will not open or the operator does not move, LiftMaster's troubleshooting chart separates several conditions. Find the one that matches what you see.

The control board powers up, but the motor does not run

LiftMaster lists these possible causes and checks (chart row):

  • Reset switch is stuck: Check reset switch.
  • Stop button active or jumper not in place for stop circuit: Check Stop button is not "stuck on", or verify that the stop button is a normally closed circuit, or put a jumper on the stop circuit.
  • If on battery power only, low or dead batteries: Charges batteries by AC or solar power or replace batteries.
  • Open or Close input active: Check all Open and Close inputs for a "stuck on" input.
  • Entrapment Protection Device active: Check all Entrapment Protection Device inputs for a "stuck on" sensor.
  • Vehicle loop detector or probe active: Check all vehicle detector inputs for a "stuck on" detector.
  • Defective control board: Replace defective control board.

The gate closes but will not open

LiftMaster lists these possible causes and checks (chart row):

  • Vehicle loop detector active: Check all vehicle detector inputs for an active detector.
  • Low battery with LOW BATT option set to CLOSE: Check if AC power is available. If no AC power, then running on batteries and battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.

The operator does not respond to a command

For wired controls such as Open, Close, or SBC, see the chart row. For remotes and transmitters, see remote control problems.

The arm moves but limits cannot be set correctly

See the chart row for "cannot set correct limits" and the chart row for "does not fully open or fully close when setting limits." See Limit and Force Adjustment.

The gate stops during travel and reverses immediately

LiftMaster lists these possible causes and checks (chart row):

  • Control (Open, Close) becoming active: Check all Open and Close inputs for an active input.
  • Vehicle loop detector active: Check all vehicle detector inputs for an active detector.
  • Low battery voltage: Battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.

Source: LiftMaster manual, 01-39383 revision B, pages 38 to 39.

Gate Opens but Will Not Close on the LiftMaster LA412UL

For a gate that opens but will not close with a transmitter or the Timer-to-Close, LiftMaster's chart (chart row) prints its causes and actions as two separate lists:

Possible causes (as printed):

  1. Open control active
  2. Vehicle loop detector active
  3. Fire Dept input active
  4. Timer-to-Close not set
  5. Close Entrapment Protection Device active

Recommended actions (as printed):

  1. Check all Open inputs for an active input
  2. Check all vehicle detector inputs for an active detector
  3. Check AC power and AC Fail option setting
  4. Check if AC power is available. If no AC power, then running on batteries and battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.
  5. Check Fire Dept input
  6. Check Timer-to-Close (TTC) setting
  7. Check all Entrapment Protection Device inputs for an active sensor

If the display shows a code, see code 60 and codes 61 to 66 and 70 to 75 for entrapment protection inputs. LiftMaster's chart also has rows for an exit loop that does not open the gate, an interrupt loop that does not stop and reverse the gate, and a shadow loop that does not keep the gate at the open limit.

Source: LiftMaster manual, 01-39383 revision B, page 39.

LiftMaster LA412UL Has No Power or the Display Is Off

If the LiftMaster LA412UL does not run and the diagnostic display is not on, LiftMaster lists these possible causes and checks (chart row):

  1. No power to control board: Check AC and battery power.
  2. Open fuse: Check fuses.
  3. If on battery power only, low or dead batteries: Charge batteries by AC or solar power or replace batteries.
  4. Defective control board: Replace defective control board.

For battery connections see Batteries. Related codes in LiftMaster's table include code 53 and code 54.

Source: LiftMaster manual, 01-39383 revision B, page 38.

LiftMaster LA412UL Remote Control Does Not Operate the Gate

For a wireless control or transmitter that does not operate a LiftMaster LA412UL gate, LiftMaster lists these causes and checks (chart row):

  1. Check XMITTER LED when wireless control is active: Activate wireless control and check XMITTER LED is on. Re-learn wireless control/transmitter to control board. Replace wireless control as needed.
  2. Stop button is active: Check Stop button is not "stuck on".
  3. Reset button is stuck: Check Reset button.
  4. Poor radio reception: Check if similar wired control operates correctly. Check if wireless controls works properly when within a few feet of operator. Check operator's antenna and antenna wire. Check other wireless controls or devices.

To re-learn a remote, see How to Program a Remote Control. If the operator's memory is full, LiftMaster notes that the memory must be erased before more remote controls can be programmed (Erase All Codes).

Source: LiftMaster manual, 01-39383 revision B, page 38.

LiftMaster LA412UL Safety Device Problems

LiftMaster's chart covers these safety device symptoms:

  • Photoelectric sensor does not stop or reverse the gate (row): Incorrect photoelectric sensor wiring: Check photoelectric sensor wiring. Retest that obstructing photoelectric sensor causes moving gate to stop, and may reverse direction. Defective photoelectric sensor: Replace defective photoelectric sensor. Retest that obstructing photoelectric sensor causes moving gate to stop, and may reverse direction.
  • Edge sensor does not stop or reverse the gate (row): Incorrect edge sensor wiring: Check edge sensor wiring. Retest that activating edge sensor causes moving gate to stop and reverse direction. Defective edge sensor: Replace defective edge sensor. Retest that activating edge sensor causes moving gate to stop and reverse direction.
  • Obstruction does not cause the gate to stop and reverse (row): Force adjustment needed: Refer to the Adjustment section to conduct the obstruction test and perform the proper force adjustment that is needed.
  • Alarm sounds for 5 minutes or with a command (row): Double entrapment occurred (two obstructions within a single activation): Check for cause of entrapment (obstruction) detection and correct. Press the reset button to shut off alarm and reset the operator.
  • Expansion board function not controlling the gate (row): Defective main board to expansionboard wiring: Check main board to expansion board wiring. If required, replace wire cable. Incorrect input wiring to expansion board: Check wiring to all inputs on expansion board. Defective expansion board or defective main board: Replace defective expansion board or defective main board.

Source: LiftMaster manual, 01-39383 revision B, pages 39 to 40.

LiftMaster LA412UL Battery and Solar Problems

The operator alarm beeps 3 times with a command when the battery is low (see chart row). Critically low battery is less than 23 V (see BATT FAIL). For solar operators, LiftMaster's chart has two rows:

  • Alarm beeps three times with a command (row): Low battery: Check if AC power is available. If no AC power, then running on batteries and battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or solar power or replace batteries.
  • Solar operator not getting enough cycles per day (row): Insufficient panel wattage: Add more solar panels. Excessive accessory power draw: Reduce the accessory power draw by using LiftMaster low power accessories. Old batteries: Replace batteries. Solar panels are not getting enough sunlight: Relocate the solar panels away from obstructions (trees, buildings, etc.).
  • Solar operator, insufficient standby time (row): Insufficient panel wattage: Add more solar panels. Excessive accessory power draw: Reduce the accessory power draw by using LiftMaster low power accessories. Battery capacity too low: Use batteries with higher amp hour (AH) rating.

Source: LiftMaster manual, 01-39383 revision B, pages 39 to 40.

LA412UL Control Board LEDs

LA412UL control board status LEDs

Swipe sideways to see all columns.

LA412UL control board status LEDs
LED State Definition (LiftMaster)
INPUT POWER OFF OFF state
INPUT POWER ON AC charger or Solar power available
BATT CHARGING OFF Not charging
BATT CHARGING ON Three stage battery charging
TIMER OFF The timer is disabled
TIMER ON The timer is enabled
TIMER MEDIUM BLINK (1 blink per second) The timer is running
TIMER FAST BLINK (2 blinks per second) The timer is paused
TIMER FASTEST BLINK (8 blinks per second) The timer is canceled
GATE MOVING OFF The gate is stopped
GATE MOVING ON The gate is opening or closing
GATE MOVING MEDIUM BLINK (1 blink per second) Operator is in E1 (single entrapment)
GATE MOVING FASTEST BLINK (8 blinks per second) The operator is in E2 (double entrapment)
BATT LOW OFF No battery error
BATT LOW ON Battery low
BATT LOW MEDIUM BLINK (1 blink per second) Battery critically low
ACC PWR OVLD OFF OFF state
ACC PWR OVLD ON Accessory overload protector opened

LA412UL control board input LEDs

Swipe sideways to see all columns.

LA412UL control board input LEDs
LED State Definition (LiftMaster)
SBC INPUT OFF Input inactive
SBC INPUT ON Input active
SBC INPUT BLINK Input active on other operator
FIRE DEPT INPUT OFF Input inactive
FIRE DEPT INPUT ON Input active
FIRE DEPT INPUT BLINK Input active on other operator
EXIT OFF Input inactive
EXIT ON Input active
EXIT BLINK Input active on other operator
SHADOW OFF Input inactive
SHADOW ON Input active
SHADOW BLINK Input active on other operator
CLOSE EYES/INTERRUPT OFF Input inactive
CLOSE EYES/INTERRUPT ON Input active
CLOSE EYES/INTERRUPT BLINK Input active on other operator
CLOSE EDGE OFF Input inactive
CLOSE EDGE ON Input active
CLOSE EDGE BLINK Input active on other operator
OPEN EYES/EDGE OFF Input inactive
OPEN EYES/EDGE ON Input active
OPEN EYES/EDGE BLINK Input active on other operator
LOCK OFF Maglock relay inactive
LOCK ON Maglock relay active

Source: LiftMaster manual, 01-39383 revision B, page 37.

Back to contents

LiftMaster LA412UL Diagnostic and Error Codes

The LiftMaster LA412UL control board shows diagnostic codes on its display. Some codes are saved in the code history and some are not; a code that is not saved briefly appears on the display as it occurs, then disappears. When cycling or disconnecting power (AC/DC) to the control board, LiftMaster recommends unplugging the J15 plug.

How to Read LA412UL Diagnostic Codes

  • To protect against fire and electrocution: DISCONNECT power (AC or solar and battery) BEFORE installing or servicing the operator.
  • For continued protection against fire: replace ONLY with a fuse of the same type and rating.

View the saved codes on the diagnostic display

  1. Press and hold the STOP button...
  2. ...then press and hold the CLOSE button...
  3. ...then press and hold the OPEN button until "Er" shows on the display.

A second later the operator will show the code sequence number followed by the code number. The first number shown is the code sequence number: "01" is the most recent code, and the display will show the sequence of codes that occurred starting with "01" and going up to code "20". The second number is the code itself (31-99, example "31"); use the table below to look it up.

To scroll through the saved codes, press the OPEN button to cycle to the most recent code ("01") and the CLOSE button to cycle to the oldest code (up to "20"). The operator will only keep track of up to 20 codes, then will start saving over the oldest codes as new codes occur.

To exit: press and release the STOP button. The display will also time out after two minutes of inactivity.

Reset the code history

  1. Press and hold the STOP button for six seconds. The display will show "Er" then "CL" alternately for six seconds.
  2. Release the STOP button. The code history has now been reset and the display will show "- -" until a new code occurs.
  3. Press and release the STOP button to exit.

Source: LiftMaster manual, 01-39383 revision B, page 34.

LiftMaster LA412UL Diagnostic Code Table

Each code below has its own anchor (for example code 60). The wording is LiftMaster's. LiftMaster's table is color-coded by category (LiftMaster system, installed system, informational, external entrapment protection, inherent entrapment protection); see the original table for the color key. The manual groups several codes that share one solution; they are listed separately here.

LiftMaster LA412UL diagnostic codes (display shows 31 to 99; code 00 is listed in the manual table)

Swipe sideways to see all columns.

LiftMaster LA412UL diagnostic codes (display shows 31 to 99; code 00 is listed in the manual table)
Code Meaning (LiftMaster) Recommended action (LiftMaster) Saved in code history Manual reference
31 Main control board has experienced an internal failure. Disconnect all power, wait 15 seconds, then reconnect power (reboot). If issue continues, replace main control board. NO Diagnostic Codes Table, page 39
32 Linear Drive Disengaged (Arm 1) Disengage then re-engage arm. Check wiring and connections. YES Diagnostic Codes Table, page 39
33 Linear Drive Disengaged (Arm 2) Disengage then re-engage arm. Check wiring and connections. YES Diagnostic Codes Table, page 39
35 Max-Run-Time Exceeded Error Check for an obstruction, then reprogram the limits. YES Diagnostic Codes Table, page 39
36 Product ID Error Was the control board just replaced? If so, erase limits, enter limit setup mode and set limits. If not, disconnect all power, wait 15 seconds, then reconnect power before changing product ID harness. YES Diagnostic Codes Table, page 39
37 Product ID Failure Unplug product ID harness then plug back in. Disconnect all power, wait 15 seconds, then reconnect power before replacing product ID harness. YES Diagnostic Codes Table, page 39
38 Hard Stop Limit (Arm 1) Limit may be set too tightly against a non-resilient hard stop (re-adjust limit). Operator may be at end of travel (re-adjust mounting). NO Diagnostic Codes Table, page 39
39 Hard Stop Limit (Arm 2) Limit may be set too tightly against a non-resilient hard stop (re-adjust limit). Operator may be at end of travel (re-adjust mounting). NO Diagnostic Codes Table, page 39
40 Battery overvoltage Too much voltage on the battery. Check harness. Make sure there is NOT a 24V battery on a 12V system. YES Diagnostic Codes Table, page 39
41 Battery overcurrent Possible short of the battery charge harness. Check harness. Make sure you do NOT have a 12V battery on a 24V system. YES Diagnostic Codes Table, page 39
42 No battery at boot up Check battery connections and installation. Replace batteries if depleted to less than 20V on a 24V system or less than 10V on a 12V system. Make sure there is NOT a single 12V battery on a 24V system. YES Diagnostic Codes Table, page 39
43 Exit Loop Error Failure or missing loop (SHORT or OPEN - LiftMaster Plug-in Loop Detector only) Check loop wiring throughout connection. May be a short in the loop, or an open connection in the loop. YES Diagnostic Codes Table, page 39
44 Shadow Loop Error Failure or missing loop (SHORT or OPEN - LiftMaster Plug-in Loop Detector only) Check loop wiring throughout connection. May be a short in the loop, or an open connection in the loop. YES Diagnostic Codes Table, page 39
45 Interrupt Loop Error Failure or missing loop (SHORT or OPEN - LiftMaster Plug-in Loop Detector only) Check loop wiring throughout connection. May be a short in the loop, or an open connection in the loop. YES Diagnostic Codes Table, page 39
46 Wireless edge battery low Replace batteries in wireless edge. YES Diagnostic Codes Table, page 39
51 Pass-point not detected (Arm 1) Check yellow pass-point wiring. If limits are not accurate, reprogram. NO Diagnostic Codes Table, page 39
52 Pass-point not detected (Arm 2) Check yellow pass-point wiring. If limits are not accurate, reprogram. NO Diagnostic Codes Table, page 39
53 Brownout occurred AC/DC board supply dipped below allowable level. Review power supply and wiring. If rebooting, ensure enough time for discharge of power to force a fresh boot. YES Diagnostic Codes Table, page 39
54 Wireless Second Operator Communication Error Check the second operator for power. If OFF, restore power and try to run the system. If powered, deactivate the wireless feature and then re-learn the second operator. YES Diagnostic Codes Table, page 39
60 Minimum number of monitored entrapment protection devices not installed. Review monitored entrapment protection device connections. This swing gate operator will operate only after installation of a minimum of one external safety device in either the open or close direction. NO Diagnostic Codes Table, page 39
61 CLOSE EYE/INTERRUPT held more than 3 minutes Check wired input on main control board; check for alignment or obstruction. YES Diagnostic Codes Table, page 39
62 CLOSE EDGE held more than 3 minutes Check wired input on main control board; check for alignment or obstruction. YES Diagnostic Codes Table, page 39
63 OPEN EYE/EDGE held more than 3 minutes Check wired input on main control board; check for alignment or obstruction. YES Diagnostic Codes Table, page 39
64 CLOSE EYE/INTERRUPT held more than 3 minutes Check wired input on expansion board; check for alignment or obstruction. YES Diagnostic Codes Table, page 39
65 CLOSE EYE/EDGE held more than 3 minutes Check wired input on expansion board; check for alignment or obstruction. YES Diagnostic Codes Table, page 39
66 OPEN EYE/EDGE held more than 3 minutes Check wired input on expansion board; check for alignment or obstruction. YES Diagnostic Codes Table, page 39
67 Wireless edge triggered more than 3 minutes Check wired input for wiring issue or obstruction. YES Diagnostic Codes Table, page 40
68 Wireless edge loss of monitoring Check wireless edge inputs. YES Diagnostic Codes Table, page 40
69 Wireless edge triggered IF an obstruction occurred, no action required. If an obstruction did NOT occur, check inputs and wiring. NO Diagnostic Codes Table, page 40
70 CLOSE EYE/INTERRUPT triggered, causing reversal, preventing close, or resetting TTC IF an obstruction occurred, no action required. If an obstruction did NOT occur, check alignment, inputs, and wiring on main control board NO Diagnostic Codes Table, page 40
71 CLOSE EDGE triggered, causing reversal, NO preventing close, or canceling TTC IF an obstruction occurred, no action required. If an obstruction did NOT occur, check alignment, inputs, and wiring on main control board NO Diagnostic Codes Table, page 40
72 OPEN EYE/EDGE triggered, causing reversal or preventing opening IF an obstruction occurred, no action required. If an obstruction did NOT occur, check alignment, inputs, and wiring on main control board NO Diagnostic Codes Table, page 40
73 CLOSE EYE/INTERRUPT triggered, causing reversal, preventing close, or resetting TTC IF an obstruction occurred, no action required. If an obstruction did NOT occur, check alignment, inputs, and wiring on expansion board. NO Diagnostic Codes Table, page 40
74 CLOSE EYE/EDGE triggered, causing reversal and preventing close or canceling TTC IF an obstruction occurred, no action required. If an obstruction did NOT occur, check alignment, inputs, and wiring on expansion board. NO Diagnostic Codes Table, page 40
75 OPEN EYE/EDGE triggered, causing reversal or preventing opening IF an obstruction occurred, no action required. If an obstruction did NOT occur, check alignment, inputs, and wiring on expansion board. NO Diagnostic Codes Table, page 40
80 Close input (EYE/EDGE) communication fault from other operator Check inputs and communication method between operators, either wired bus or radio. Ensure operator is powered. May have to erase the wireless communication and reprogram the two operators. YES Diagnostic Codes Table, page 40
81 Open input (EYE/EDGE) communication fault from other operator Check inputs and communication method between operators, either wired bus or radio. Ensure operator is powered. May have to erase the wireless communication and reprogram the two operators. YES Diagnostic Codes Table, page 40
82 Close input (EYE/EDGE) communication fault (expansion board) Check the connections between the main board and the expansion board. YES Diagnostic Codes Table, page 40
83 Open input (EYE/EDGE) communication fault (expansion board) Check the connections between the main board and the expansion board. YES Diagnostic Codes Table, page 40
84 Non-monitored device detected on the wireless safety system Non-monitored contact closure devices are not supported. Make sure connected devices are monitored. Check edges for proper orientation and resistive end cap connection. YES Diagnostic Codes Table, page 40
91 Force Reversal (Operator 1) Check for obstruction. If no obstruction, check that the mechanical assembly is engaged and free to move. See section on Limit and Force Adjustment, and Obstruction Test. YES Diagnostic Codes Table, page 40
92 Force Reversal (Operator 2) Check for obstruction. If no obstruction, check that the mechanical assembly is engaged and free to move. See section on Limit and Force Adjustment, and Obstruction Test. YES Diagnostic Codes Table, page 40
93 RPM / STALL Reversal (Operator 1) Check for obstruction. If no obstruction, check the operator wiring and that the mechanical assembly is engaged and free to move. Replace APE assembly. YES Diagnostic Codes Table, page 40
94 RPM / STALL Reversal (Operator 2) Check for obstruction. If no obstruction, check the operator wiring and that the mechanical assembly is engaged and free to move. Replace APE assembly. YES Diagnostic Codes Table, page 40
99 Normal Operation No action required YES Diagnostic Codes Table, page 40

Back to contents

LiftMaster LA412UL Maintenance

LiftMaster's maintenance instructions for the LA412UL are on page 36 of the manual (document 01-39383 revision B). Disconnect all power (AC, solar, battery) to the operator before servicing. The operator's AC power switch ONLY turns off AC power to the control board and DOES NOT turn off battery power. ALWAYS disconnect the batteries to service the operator.

Important Safety Instructions

To reduce the risk of SEVERE INJURY or DEATH:

  • READ AND FOLLOW ALL INSTRUCTIONS.
  • ANY maintenance to the operator or in the area near the operator MUST NOT be performed until disconnecting the electrical power (AC or solar and battery) and locking-out the power via the operator power switch. Upon completion of maintenance the area MUST be cleared and secured, at that time the unit may be returned to service.
  • Disconnect power at the fuse box BEFORE proceeding. Operator MUST be properly grounded and connected in accordance with national and local electrical codes. NOTE: The operator should be on a separate fused line of adequate capacity.
  • NEVER let children operate or play with gate controls. Keep the remote control away from children.
  • ALWAYS keep people and objects away from the gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
  • The entrance is for vehicles ONLY. Pedestrians MUST use separate entrance.
  • Test the gate operator monthly. The gate MUST reverse on contact with an object or reverse when an object activates the noncontact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of INJURY or DEATH.
  • Use the manual disconnect release ONLY when the gate is NOT moving.
  • KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.
  • ALL maintenance MUST be performed by a LiftMaster professional.
  • Activate gate ONLY when it can be seen clearly, is properly adjusted and there are no obstructions to gate travel.
  • To reduce the risk of FIRE or INJURY to persons use ONLY LiftMaster part 29-NP712 for replacement batteries.
  • SAVE THESE INSTRUCTIONS.
  • ALWAYS wear protective gloves and eye protection when changing the battery or working around the battery compartment.

Source: LiftMaster manual, 01-39383 revision B, page 36.

Maintenance Chart

LiftMaster LA412UL maintenance chart: check at least once every month, 6 months, or 3 years

Swipe sideways to see all columns.

LiftMaster LA412UL maintenance chart: check at least once every month, 6 months, or 3 years
Description Task Month 6 months 3 years
Entrapment protection devices Check and test for proper operation X
Warning signs Make sure they are present and replace if worn or broken X
Manual release Check and test for proper operation X
Gate Inspect for wear or damage; ensure it still complies with ASTM F2200, see page 5 X
Accessories Check all for proper operation X
Electrical Inspect all wire connections X
Mounting hardware Check for tightness X
Operator Inspect for wear or damage X
Batteries Replace X

LiftMaster's notes: severe or high cycle usage will require more frequent maintenance checks. It is suggested that while at the site, voltage readings be taken at the operator. Using a digital voltmeter, verify that the incoming voltage to the operator is within ten percent of the operator's rating.

Batteries

Batteries will degrade over time depending on temperature and usage. The operator alarm will beep 3 times with a command if the battery is low. Batteries do not perform well in extremely cold temperatures. For best performance, the batteries should be replaced every 3 years. Use only LiftMaster part 29-NP712 for replacement batteries. The batteries contain lead and need to be disposed of properly. Two 33AH batteries (A12330SGLPK) may be used in place of the 7AH batteries for a large metal control box solar installation; a battery tray (K10-36183) and battery harness (K94-37236) are required for 33AH applications. Shop gate operator batteries.

Source: LiftMaster manual, 01-39383 revision B, page 36.

Back to contents

LiftMaster LA412UL Repair and Replacement Parts

The tables below list the LA412UL repair parts and part numbers as printed by LiftMaster on page 46 of manual 01-39383 revision B: the standard control box (items 1 to 7) and the gate operator arm (items 1 to 5), with the parts LiftMaster lists as "not shown."

All Security Equipment note: using these links. The part numbers and descriptions are LiftMaster's. The links in the right-hand column open our category pages or search our catalog for the part number; they do not by themselves confirm that we stock a part or that it fits your operator.

Browse by category: gate operator parts | control boards | motors | batteries | gate operator accessories

LiftMaster LA412UL repair parts as listed by LiftMaster (page 47)

Swipe sideways to see all columns.

LiftMaster LA412UL repair parts as listed by LiftMaster (page 47)
Part (LiftMaster description) LiftMaster part number Related manual section Find at All Security Equipment
Standard Plastic Control Box Only (item 1) K94-39307-3 Repair parts, page 46 Search K94-39307-3
Reset Switch with Product ID (item 2) K94-36408-3 Repair parts, page 46 Search K94-36408-3
Piezo Alarm (item 3) K94-36411 Repair parts, page 46 Search K94-36411
Control Board Bracket (item 4) K75-36635 Repair parts, page 46 Search K75-36635
Control Board (item 5) K1D8388-1CC Repair parts, page 46 Browse control boards | Search K1D8388-1CC
Battery (item 6) 29-NP712 Repair parts, page 46 Browse batteries | Search 29-NP712
Solar Panel (item 7) SP10W12V Repair parts, page 46 Search SP10W12V
Primary Arm (arm item 1) LA412DC Repair parts, page 46 Search LA412DC
Release Lever (arm item 2) 041ASWG-0442SA Repair parts, page 46 Search 041ASWG-0442SA
Motor with Limit Switch Harness (arm item 3) 041ASWG-0594SA Repair parts, page 46 Browse motors | Search 041ASWG-0594SA
Rear Connector (arm item 4) 041ASWG-0014SA Repair parts, page 46 Search 041ASWG-0014SA
Cable 12 V with Connector (arm item 5) 041ASWG-0597SA Repair parts, page 46 Search 041ASWG-0597SA

Additional LA412UL parts listed by LiftMaster as "not shown" in the diagram (page 47)

Swipe sideways to see all columns.

Additional LA412UL parts listed by LiftMaster as "not shown" in the diagram (page 47)
Part (LiftMaster description) LiftMaster part number Find at All Security Equipment
Metal Control Box Only K74-36806-5 Search K74-36806-5
J15 Harness K94-36891 Search K94-36891
Antenna K77-36541 Search K77-36541
Standard Plastic Control Box with Control Board LA412CONTUL Search LA412CONTUL
Large Metal Control Box for Solar Applications XSOLARCONTUL Search XSOLARCONTUL
Release Key 041ASWG-0119 Search 041ASWG-0119
Hardware Bag Complete with: gate bracket, post bracket, pull-to-open bracket and hardware K77-19130 Search K77-19130

Source: LiftMaster manual, 01-39383 revision B, page 46.

Back to contents

Compatible LA412UL Accessories

LiftMaster's manual lists the following accessories for the LA412UL (pages 49 to 50). Model numbers are LiftMaster's; the links go to related All Security Equipment categories and do not by themselves confirm that we stock an item or that it fits your operator.

Entrapment Protection Devices

LiftMaster monitored devices are required for UL 325 entrapment protection (see Installing Entrapment Protection Devices). Shop photoelectric sensors and edge sensors.

  • LMTBUL and LMTBU, monitored through beam photoelectric sensors
  • LMRRUL and LMRRU, monitored retro-reflective photoelectric sensors
  • CPS-UN4 and CPSUN4G, LiftMaster Monitored Commercial Protector System
  • LMWEKITU, monitored wireless edge kit (transmitter and receiver)
  • LMWETXU, monitored wireless edge transmitter
  • L50 (large profile monitored edge, 82 ft. roll) and L50E (ends kit, 10 pair)
  • S50 (small profile monitored edge, 82 ft. roll) and S50E (ends kit, 10 pair)
  • L50CHP (plastic channel, 8 ft., pack of 10) and L50CHAL (aluminum channel, 10 ft., pack of 8)
  • L504AL, L505AL, L506AL (large profile monitored edges, 4, 5, 6 ft.)
  • S504AL, S505AL, S506AL (small profile monitored edges, 4, 5, 6 ft.)
  • ETOOL, edge cutting tool

Remote Controls and Access Devices

LiftMaster's remote controls are compatible with operators manufactured by LiftMaster after 1993. Shop gate remote controls and keypads.

  • 893MAX, 3-button remote control (includes visor clip)
  • 890MAX, 3-button mini-remote control (includes key ring and fastening strip)
  • 892LT and 894LT, Security+ 2.0 learning remote controls
  • 877MAX, keyless entry (4-digit code keypad)
  • KPW250, wireless commercial keypad (Security+ 2.0 compatible)
  • STAR1000, commercial access control receiver (up to 1,000 devices)
  • 86LM, remote antenna extension kit
  • CAPXL, LiftMaster Cloud connected access protocol, high capacity

Operator Accessories

  • LOOPDETLM, plug-in loop detector (low power; plugs into the existing control board). Search for LOOPDETLM or browse loop detectors.
  • LD7LP, low power loop detector mounted and wired separately inside the control box
  • CP3, vehicle sensing probe
  • 50-19503, push-to-open bracket (used to allow the gate operator to push the gate open)
  • MG1300, outdoor magnetic lock with transformer, junction box, mounting plate and hardware (not for use with solar applications; must be powered separately). Shop magnetic locks.
  • APOW3, transformer
  • K1D8387-1CC, expansion board (additional programming features including external loops, plug-in loops, auxiliary relays, and inputs for additional controls and entrapment protection devices)
  • K94-34778, wire harness between the main control board and the expansion board
  • SP10W12V (10 Watt, 12V) and SP20W12V (20 Watt, 12V), solar panel kit (60W maximum for 24 Vdc operators and 30W maximum for 12 Vdc operators; requires a 33AH battery harness). Browse solar panels and accessories.
  • 40-39235, warning sign

Batteries and Battery Hardware

  • 29-NP712, standard 7AH 12 Vdc battery (reuse existing harnesses)
  • A12330SGLPK, upgrade 33AH 12 Vdc battery (ideal for solar applications and extended battery backup; for use with the large metal control box only)
  • K10-36183, battery tray (required for 33AH applications)
  • K94-37236, universal solar wire harness kit (for 7AH and 33AH applications). Search for K94-37236.

Two identical 12 Vdc batteries are required for each gate operator. Do not mix 7AH and 33AH batteries within a gate operator. Shop gate operator batteries.

Source: LiftMaster manual, 01-39383 revision B, pages 49 to 50.

Back to contents

Frequently Asked Questions About the LiftMaster LA412UL

What size gate can the LA412UL move?

Per the manual (page 7), the maximum gate weight depends on gate length: 850 lbs. (385.6 kg) at 10 ft (3.0 m), 750 lbs. (340.2 kg) at 12 ft (3.7 m), 650 lbs. (294.8 kg) at 14 ft (4.3 m), and 550 lbs. (249.5 kg) at 16 ft (4.9 m). The 90 degree travel time is under 23 seconds, the maximum travel range is 115 degrees, and the maximum daily cycle rate is 50 cycles per day. See Specifications.

How do I set the limits?

With the GATE switch on 1, press SET OPEN and SET CLOSE together to enter limit setting mode, move the gate with the MOVE GATE buttons and press SET OPEN or SET CLOSE at each limit, then cycle the gate with the TEST BUTTONS to set the force (pages 26 and 27). Limits can also be set with a 3-button remote control (page 45). See Limit and Force Adjustment.

How do I open the gate by hand?

Insert the key, turn it 180° counter-clockwise, then turn the release lever 180° counter-clockwise. To engage again, turn the release lever and then the key 180° clockwise. Use the release only when the gate is not moving. See Manual Release.

What entrapment protection does the LA412UL need?

Per the manual, a minimum of two independent monitored entrapment protection devices are required at each entrapment zone; the inherent device built into the operator serves as one of the two, and swing gate operators require the first external monitored device to function. The installer must protect ALL entrapment zones in both the open and close cycles (pages 3 and 20). See Installing Entrapment Protection Devices.

What batteries does the LA412UL use?

LiftMaster says to use only part 29-NP712 for replacement batteries and recommends replacing them every 3 years. The standard control box uses 7AH batteries; two 33AH batteries (A12330SGLPK) with a battery tray (K10-36183) and battery harness (K94-37236) may be used in a large metal control box solar installation (page 36). See Batteries and Install Solar Panels.

Does the LA412UL run on AC power?

No. The manual lists the main AC supply as "N/A - Solar Only." The operator runs on 12 Vdc batteries charged by solar panels (30 watts maximum). See Install Solar Panels and Specifications.

What warranty does the LA412UL have?

Per the manual, LiftMaster's warranty is a two year limited warranty from the date of purchase. The warranty terms, including exclusions, are printed on page 51 of the manual.

Where is the wiring diagram?

The standard control box wiring diagram is on page 47 and the large metal control box wiring diagram is on page 48 of LiftMaster's installation manual. See the wiring diagram section.

Back to contents

Original LiftMaster LA412UL Documentation

This HTML resource is presented by All Security Equipment, is not a LiftMaster publication, and does not replace the original manufacturer documentation. It is based on LiftMaster's LA412UL installation manual, document 01-39383, revision B (© 2018 The Chamberlain Group, Inc.), which covers the LA412PKGUL, LA412DC, and LA412DCS.

Check the product page for the current revision before relying on any document, because LiftMaster may update them.

Back to contents